34
Select the required sub-function
oP2
:
on1
Time oP2 turns
on
first time
oP2
:
oFF1
Time oP2 turns
off
first time
oP2
:
on2
Time oP2 turns
on
second time
oP2
:
oFF2
Time oP2 turns
off
second time
When selected pressing
(
will show the existing
time with the hours flashing. Using the
*
or
&
button adjust the hours and then press
(
to transfer
control to the minutes display, pressing
(
again will
transfer control to the seconds display. When the
time has been set as required press
)
to return to
the sub-menu from which another
on
/
off
time may
be selected for adjustment. When all the
on
/
off
times have been entered, return to the configuration
menu by pressing the
)
button twice.
8.4.13 Access control output
on
&
off
times
from display mode:
AC5P
This function activates a separate menu that
provides direct access to the control output's
on
and
off
times when the Clock is the display mode
(displaying time). An operator may therefore adjust
the
on
and
off
times without having access to the
instrument configuration menu. Further protection is
provided by a separate security code. When this
function is enabled the
on
and
off
times of the two
control outputs may be adjusted from the display
mode by simultaneously operating the
(
and
*
push buttons. The function contains two sub-
functions,
EnbL
which activates the function and
ACCd
which defines a separate access code that may
be used to prevent the
on
and
off
times being
accidentally adjusted from the display mode.
To check or change the function, select
AC5P
in the
configuration menu and press
(
which will reveal
the
EnbL
prompt, pressing
(
again will show if the
function is
on
or
oFF
. If adjustment of the control
output times from the display mode is not required
press the
*
or
&
button to select
off
and then
press
)
twice to return to the configuration menu.
If the function is required, select
on
and press
)
to
return to the
EnbL
prompt from which
ACCd
, which
allows a separate access code to be entered, can be
selected by pressing the
*
or
&
button.
Access to the control output times from the display
mode may be protected by a four digit alphanumeric
security code which must be entered to gain access.
Default security code
0000
allows unrestricted
access. With
ACCd
displayed, press
(
to enter a
new access code. The BA577E-SS Clock will
display
0000
with one digit flashing. The flashing
digit may be adjusted using the
*
or
&
push
button, when set as required operating the
(
button
will transfer control to the next digit. When all the
digits have been adjusted press
)
twice to return to
the
AC5P
prompt in the configuration menu. The
revised security code will be activated when the
BA577E-SS is returned to the display mode.
8.4.14 Security code:
CodE
Access to the instrument's configuration menu may
be protected by a four digit alphanumeric security
code which must be entered to gain access. New
instruments are configured with the default security
code
0000
which allows unrestricted access to all
configuration functions.
To enter a new security code select
CodE
from the
configuration menu and press
(
which will cause
the Clock to display
0000
with one digit flashing. The
flashing digit may be adjusted using the
*
and
&
push button, when set as required operating the
(
button will transfer control to the next digit.
When all the digits have been adjusted press
)
to
return to the
CodE
prompt. The revised security code
will be activated when the Clock is returned to the
display mode.
Please contact BEKA associates sales department if
the security code is lost.
8.4.15 Reset configuration to Clock factory
defaults:.
r5Et dEF
When the BA577E-SS is configured as a Clock, this
function resets the configuration to the Clock factory
defaults shown in sections 8.4 of this manual.
To reset the instrument configuration select
r5Et dEF
from the configuration menu and press
(
.
The Clock will display
0000
with the first digit flashing
which is a request to confirm the instruction by
entering
5urE
. Using the
*
or
&
button set the
first flashing digit to
5
and press
(
to transfer
control to the second digit which should be set to
u
.
When
5urE
has been entered pressing the
)
button
will reset all the configuration functions to the factory
defaults and return the instrument to the display
mode as a Clock with default configuration.