5.2  Accessing the configuration and   
       calibrations functions.

Throughout this manual push buttons are shown
as 

P

,  

  E

,

   

 

or  

, and legends displayed by the

Rate Totaliser are shown within inverted commas
e.g. 'CAL' and ' ALr2'.

Access to the configuration menu is obtained by
operating  the

 

P

 and

 

E

 push  

buttons

simultaneously.    If  the  Rate  Totaliser’s  security
code is set to the default 0000 the first parameter
'FunC' will be displayed.  If a security code other
than  the  default  code  0000  has  already  been
entered,  the  Rate  Totaliser  will  display  'CodE'.
Pressing  the  

P

  button  will  clear  this  prompt

allowing each digit of the code to be entered using
the 

 and

 

 push buttons and the  

P

 button to

move control to the next digit.  When the correct
four digit code has been entered pressing

 

E

 will

cause the first parameter 'FunC' to be displayed.
If the code is incorrect, or a button is not pressed
within  twenty  seconds,  the  Rate  Totaliser  will
automatically return to the display mode. 

Once  within  the configuration  menu  the required
parameter can be reached by scrolling through the
menu using the 

 and 

 

push buttons as shown

in Fig 8.    When returning to the display mode
following recalibration or a change to any function,
the Rate Totaliser will display  ‘dAtA’ followed by
‘SAVE’ while the new information is stored in non-
volatile memory.

All new Rate Totalisers are supplied calibrated as
requested at the time of ordering.  If calibration is
not requested, Rate Totalisers will be supplied with
the following default configuration:

Default Configuration

Access code  ‘CodE’

  

0000

Function  ‘FunC’

‘5td’ Linear

Rate display at 4mA  ‘Zero’

0.00

Rate display at 20mA  ‘5PAn’

100.00

Resolution  ‘rE5n’

1 digit

P

 button in display mode ‘C—P’

%

Local reset of total  ‘t-rE5Et’

off

Local reset of grand total ‘Gt-rE5Et’ off
Clip off  ‘CLIP oFF’

000.00

Timebase   ‘t-bA5E’

1

Total scale factor  ‘5CALE-t’

1.00 

Upper display   ‘di5P-1’

Total

Update time  ‘uPdAtE’

1

5.3  Summary of configuration functions

This  section  summarises  each  of  the  main
configuration  functions  and  includes  a  cross
reference   to   a   more   detailed   description.     Fig   8
illustrates the location of each function within the
configuration  menu.    The  lineariser  and  the
optional  factory  fitted  alarms  are  described
separately in sections 6 and 9.3 of this manual.

  

Display

      Summary of function

'FunC'

Rate Totaliser function

Defines the relationship between the
4/20mA  input  current  and  the
instruments rate display.  
For uni-directional flow may be set
to:
 ‘5td’

Standard linear relationship

 ‘root’ Square root extraction
 ‘Lin’

16 segment adjustable 
lineariser – see section 6

For bi-directional flow may be set 
to:
 ‘bi-5td’ Standard linear relationship
 ‘bi-Lin’ 16 segment adjustable 

lineariser – see section 6

See section 5.4

'rE5n'

Display resolution

Defines  the  resolution  of  the  least
significant rate display digit.  May be
set to ‘1’, ‘2’, ‘5’ or ‘10’ digits.
See section 5.5

‘uPdAtE’

Update

Defines  the  interval  between
updates.  May be set to ‘1’, ‘2’, ‘3’,
‘4’ or ‘5’ seconds.
See section 5.6

‘di5P-1’

Upper display

Defines whether  ‘totAL’  or  ‘rAtE’  is
shown  on  the  upper  eight  digit
display.
See section 5.7

‘di5P-2’

Lower display

Turns lower six digit display ‘on’ or
‘oFF’.
See section 5.8

'dP'

Decimal points

Positions  the  decimal  point  in  the
‘rAtE’ and ‘totAL’ displays.
See section 5.9

9

Содержание BA558E

Страница 1: ...Issue 3 4th July 2014 BA558E General Purpose 4 20mA loop powered panel mounting Rate Totaliser Issue 3...

Страница 2: ...ion using external current source 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error...

Страница 3: ...vated Loading message displayed Configuration message displayed Model and firmware version displayed The BA558E Rate Totaliser starts functioning using configuration information stored in the instrume...

Страница 4: ...mode Operating the or button will toggle the display to CLr YE5 with YE5 flashing operating the E button will then clear the grand total and Gt CLrd will be displayed to confirm the operation The ins...

Страница 5: ...nce of less than 1k as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the...

Страница 6: ...3 Installation Procedure a Cut the specified aperture in the panel To achieve an IP66 seal between the instrument enclosure and the instrument panel the aperture must have the tighter tolerances spec...

Страница 7: ...as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it...

Страница 8: ...lay at 20mA are adjustable although for flow application the display at 4mA is usually zero The position of the decimal point in the rate display is defined by the dP function To simplify calibration...

Страница 9: ...onfiguration Access code CodE 0000 Function FunC 5td Linear Rate display at 4mA Zero 0 00 Rate display at 20mA 5PAn 100 00 Resolution rE5n 1 digit P button in display mode C P Local reset of total t r...

Страница 10: ...s operated in the display mode Select PC of 4 20mA input 4 20 Current in mA Note PC is not available with lineariser See section 5 14 Display Summary of function 5CALE t Total scale factor Defines the...

Страница 11: ...ntains two sub functions Select ConF Returns instrument to default configuration shown in section 5 2 LtAb Returns lineariser to defaults shown in section 6 5 Both instructions must be confirmed by en...

Страница 12: ...12...

Страница 13: ...arity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Страница 14: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Страница 15: ...s been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Страница 16: ...he or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of...

Страница 17: ...g the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated...

Страница 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is require...

Страница 19: ...19...

Страница 20: ...llowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Страница 21: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Страница 22: ...er the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or butt...

Страница 23: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Страница 24: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Страница 25: ...tly the following table may help to identify the cause of the failure Symptom Cause Check No display and no voltage between terminals 1 3 or 12 3 if optional backlight is loop powered No power supply...

Страница 26: ...New Rate Totalisers are supplied with the tag or application information specified when ordered thermally printed onto the rear panel adjacent to the terminals This tag information is not visible fro...

Страница 27: ...sed and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 12 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any...

Страница 28: ...28...

Страница 29: ...ivated when the selected display rate or total equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally cl...

Страница 30: ...y pressing the or button followed by the E button to return to the alarm menu 9 3 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Страница 31: ...ate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are...

Страница 32: ...to the display mode Fig 15 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may b...

Страница 33: ...backlight 9 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the Rate Totaliser s 4 20mA input as shown in Fig 17 which increases the maximum Rate Totalis...

Отзывы: