5.11  Calibration of the rate display using 
         internal reference:   ‘5Et’

Using  the  ‘5Et’  function  the  rate  display  can  be
calibrated without the need to know the value of
the  4/20mA  input  current,  or  to  disconnect  the
BA558E Rate Totaliser from the 4/20mA loop.  

When  using  the  ‘5Et’  function  the  instrument’s
internal reference is used to simulate a 4mA and
20mA input current.  

Zero

  rate display with a simulated 4mA input

Span

 rate display with a simulated 20mA input

To calibrate the rate display select '5Et' from the
configuration  menu  and  press

 

P

.    

The  Rate

Totaliser will display 'ZEro', pressing  

P

 again will

reveal  the  current  rate  display  at  4mA.      The
flashing digit can be adjusted by pressing the 

 or

 buttons, when set as required pressing  

P

 

will

transfer  control  to  the  next  digit.    When  all  the
digits have been adjusted, press 

E

 to return to the

'ZEro' prompt.

To adjust the rate display at 20mA, press the 

button   which   will   cause   the   Rate   Totaliser   to
display  '5PAn',  pressing  

P

 

will  then  reveal  the

existing rate display at 20mA.   The flashing digit
can be adjusted by pressing the 

 or 

 buttons,

when  set  as  required  pressing  

P

 will  transfer

control to the next digit.  When all the digits have
been adjusted press 

E

 

twice

 t

o return to the '5PAn'

prompt followed and then to the ‘5Et’ prompt in the
configuration menu.

5.12  Clear grand total:   ‘Clr.Gtot’

The grand total is a separate sixteen digit counter
which duplicates the total display but is not zeroed
when the total display is reset to zero.  The grand
total may be viewed in the operating mode in two
eight digit sections as described in section 2.1 of
this manual.   The following table illustrates how
grand totals are displayed.

        Grand total        High display  Low display

1234567890123456

12345678

90123456

-1234

-1234

-12345678

-

12345678

-1234567890

-12

32567890

-123456789012345

-1234567

89012345

The grand total counter can be reset to zero from
the 'CLr.Gtot' function in the configuration menu, or
from  the  operating  mode  if  the  local  grand  total
reset has been activated, see section 5.17.   

To  zero  the  grand  total  from  within  the
configuration menu select   'Clr.Gtot' and press  

P

which will cause the instrument to display 'Clr.no'.
Press  the  

 or  

 button  until  'CLr.YE5'  is

displayed and then press  

P

 which will result in a

'0000' prompt.  Using the 

 and

 

 buttons and

the

 

P

 button to move to the next digit, enter '5urE'

digit by digit to confirm the instruction.   Pressing

 

E

will  then  reset  the  grand  total  counter  to  zero,
briefly  displaying  ‘Gt  CLrd’  to  confirm  that  the
instruction  has  been  performed  and  return  the
instrument  to  the  'CLr.Gtot'  prompt  in  the
configuration menu.  

CAUTION

After resetting the original grand

total can not be recovered.

5.13  Timebase:  t-bA5E

Together with the total scale factor '5CALE-t', this
function  defines  the  arithmetic  relationship
between  the  rate  and  total  displays.        The
timebase divides the rate display by 1, 60 or 3,600
depending upon whether the BA558E rate display
represents  flow  per  second,  per  minute  or  per
hour.    See Fig 6.

To check or change the timebase select 't-bA5E'
from the configuration menu and press 

P

 which will

reveal the current setting.   Pressing the 

 or 

button will index though the following three options.

BA558E

Rate display

Represents

flow

Select

in

t-bA5E

menu

Total display

= rate display

divided by

Per second

‘tb – 1’

1

Per minute

‘tb – 60’

60

Per hour

‘tb – 3600’

3600

After  selecting  the  required  divisor,  press  

E

 to

return to the ‘t-bA5E’ prompt in the configuration
menu.

5.14  Function of the 

P

  push-button:   ‘C - - P’

When the Rate Totaliser is in the operating mode,
operating the  

P

 push button will display the input

current in milliamps, or the displayed flow rate as a
percentage of the difference between the displayed
flow rate at 4mA and 20mA inputs.  

To  check  or  change  the  function  of  the  

P

 push

button select 'C - -P' from the configuration menu
and press 

P

 to reveal the current setting.  Pressing

the 

 or 

 button will toggle the setting between

'4-20' the current display in milliamps and 'PC' the
percentage display.   When set as required press

E

  to  return  to  the  ‘C  -  -  P’  prompt  in  the

configuration menu.   

Note:

  The percentage option ‘PC’ is not available

when  the  sixteen  segment  lineariser  is  selected
see section 5.4.

15

Содержание BA558E

Страница 1: ...Issue 3 4th July 2014 BA558E General Purpose 4 20mA loop powered panel mounting Rate Totaliser Issue 3...

Страница 2: ...ion using external current source 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error...

Страница 3: ...vated Loading message displayed Configuration message displayed Model and firmware version displayed The BA558E Rate Totaliser starts functioning using configuration information stored in the instrume...

Страница 4: ...mode Operating the or button will toggle the display to CLr YE5 with YE5 flashing operating the E button will then clear the grand total and Gt CLrd will be displayed to confirm the operation The ins...

Страница 5: ...nce of less than 1k as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the...

Страница 6: ...3 Installation Procedure a Cut the specified aperture in the panel To achieve an IP66 seal between the instrument enclosure and the instrument panel the aperture must have the tighter tolerances spec...

Страница 7: ...as an accessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it...

Страница 8: ...lay at 20mA are adjustable although for flow application the display at 4mA is usually zero The position of the decimal point in the rate display is defined by the dP function To simplify calibration...

Страница 9: ...onfiguration Access code CodE 0000 Function FunC 5td Linear Rate display at 4mA Zero 0 00 Rate display at 20mA 5PAn 100 00 Resolution rE5n 1 digit P button in display mode C P Local reset of total t r...

Страница 10: ...s operated in the display mode Select PC of 4 20mA input 4 20 Current in mA Note PC is not available with lineariser See section 5 14 Display Summary of function 5CALE t Total scale factor Defines the...

Страница 11: ...ntains two sub functions Select ConF Returns instrument to default configuration shown in section 5 2 LtAb Returns lineariser to defaults shown in section 6 5 Both instructions must be confirmed by en...

Страница 12: ...12...

Страница 13: ...arity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Страница 14: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Страница 15: ...s been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Страница 16: ...he or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of...

Страница 17: ...g the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated...

Страница 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is require...

Страница 19: ...19...

Страница 20: ...llowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Страница 21: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Страница 22: ...er the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or butt...

Страница 23: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Страница 24: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Страница 25: ...tly the following table may help to identify the cause of the failure Symptom Cause Check No display and no voltage between terminals 1 3 or 12 3 if optional backlight is loop powered No power supply...

Страница 26: ...New Rate Totalisers are supplied with the tag or application information specified when ordered thermally printed onto the rear panel adjacent to the terminals This tag information is not visible fro...

Страница 27: ...sed and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 12 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any...

Страница 28: ...28...

Страница 29: ...ivated when the selected display rate or total equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally cl...

Страница 30: ...y pressing the or button followed by the E button to return to the alarm menu 9 3 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Страница 31: ...ate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are...

Страница 32: ...to the display mode Fig 15 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may b...

Страница 33: ...backlight 9 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the Rate Totaliser s 4 20mA input as shown in Fig 17 which increases the maximum Rate Totalis...

Отзывы: