e.g.  An  Rate Totaliser with a high alarm set at
9000  and  an  alarm  delay  of  30  seconds  will
perform as follows:

The alarm annunciator will start to flash when an
increasing rate display equals 9000, but the alarm
output  will  not  be  activated  until  the  alarm
condition has existed continuously for 30 seconds.
When  the  alarm  output  is  activated,  the  alarm
annunciator  will  stop  flashing  and  become
permanently activated.

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs, has been
enabled, it will not start to function until the alarm
output is activated.  
See section 9.2.11.

9.2.10  Alarm silence time:   5iL

This function is primarily intended for use in small
installations  where  the  alarm  output  directly
operates an alarm annunciator such as a sounder
or beacon.  When the alarm silence time, which is
adjustable  between  0  and  3600  seconds  in  1
second increments, is set to any figure other than
zero, the 

P

 push-button becomes an alarm accept

button.   After an alarm has occurred, operating the

P

 button will cause the alarm output to revert to the

non-alarm  condition  for  the  programmed  alarm
silence time.  If the alarm condition still exists at
the end of the silence time, the alarm output will be
reactivated.    During  the  silence  time  the  Rate
Totaliser  alarm  annunciator  will  flash  until  the
silence time expires or the alarm is cleared. 

If  the  ‘FL5H’  function,  which  flashes  the  Rate
Totaliser display when an alarm occurs has been
enabled,  it  will  only  function  when  the  alarm
output  is  activated,  not  during  the  silence  time.
See section 9.2.11.

To adjust the alarm silence time select '5iL' from
the alarm configuration menu and press  

P

 which

will reveal the existing silence time.   The flashing
digit of the silence time can be adjusted using the

 and 

 push-buttons, and the 

P

 button to move

control  to  the  other  digits.    When  the  required
silence time has been entered press 

E

 

to return to

the alarm menu.

9.2.11 Flash display when alarm occurs

 

‘FL5H’

In addition to the two alarm annunciators on the
Rate  Totaliser  display  which  show  the  status  of
both alarms, this function provides an even more
conspicuous indication that an alarm condition has
occurred.    

When enabled, the rate or total display depending
upon  which  has  caused  the  alarm,  alternates
between   the   numerical   value   and   the   alarm

reference, ‘ALr1’ or ‘ALr2’ when the alarm output is
activated.  If both alarm outputs are activated by
one  variable,  the  display  alternates  between  the
numerical value and ‘Alr1-2’.

To  enable  or  disable  the  function  select  'FL5H'
from the alarm menu and press 

P

 which will reveal

the current setting.  The function can be changed
by pressing the 

 or 

 button followed by the  

E

button to return to the alarm menu.

9.2.12  Access setpoint in display mode:  

         AC5P

This function enables a separate menu providing
access  to  the  alarm  setpoints  from  the  display
mode  by  simultaneously  operating  the  

P

 and  

push buttons.  An operator can therefore adjust the
alarm setpoints without having access to the Rate
Totaliser  configuration  menu.    Protection  against
accidental  adjustment  of  the  setpoints  when  the
Rate Totaliser is in the display mode is provided by
a separate security code.

This direct setpoint access menu is enabled and
the separate security code entered from the 'AC5P'
function in the alarm configuration menu as shown
in Fig 13.  To change the menu parameters select
'AC5P' from the configuration menu and press  

P

which will display the enable prompt 'EnbL'.  Press

P

 again to reveal if the direct access menu is 'on'

or 'oFF'.  The 

 or 

 button will toggle the display

between the two conditions.  

If  'oFF'  is  selected,  the  operator  will  not  have
access  to  the  setpoints  from  the  display  mode.
Return to the 'AC5P' prompt in the main menu by
pressing

 

E

 twice.  

If  'on'  is  selected,  the  operator  will  have  direct
access  to  the  alarm  setpoints  from  the  display
mode via a separate optional security code.   To
define this four digit security code press 

P

 to return

to the 'Enbl' prompt followed by the 

 or 

 button

to  select  the  access  code  prompt  'ACCd'.
Pressing  

P

 

will  reveal  the  current  security  code.

Each  digit  of  the  code  may  be  changed  by
operating the 

 and 

 push buttons, and the  

P

button to move control to the next digit.  When the
required code has been entered, press 

E

 twice to

return  to  the  'AC5P'  prompt  in  the  configuration
menu.

Default  code  0000  will  disable  the  security  code
allowing  direct  access  to  the  setpoints  in  the
display  mode  by  pressing  the

 

P

 

and  

 buttons

simultaneously.  Unless otherwise requested new
instruments  with  alarms  are  supplied  with  this
function  disabled  and  the  security  code  set  to
0000.

31

Содержание BA554E

Страница 1: ...Issue 3 4th July 2014 BA554E General Purpose 4 20mA loop powered field mounting Rate Totaliser Issue 3 ...

Страница 2: ...urce 6 1 1 Example Adding break points to a new Rate Totaliser 6 2 Calibration using internal reference 6 2 1 Example Adding break points to a new Rate Totaliser 6 3 Error messages 6 4 Under and over range 6 5 Default configuration 7 Calibration Examples 7 1 Using an external current source 7 2 Using the internal reference 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding afte...

Страница 3: ... twelve seconds All segments of the display are activated Loading message displayed Configuration message displayed Model and firmware version displayed Rate Totaliser starts functioning using configuration information stored in instrument s permanent memory Unless total and grand total displays have been reset to zero new flow will be added to the existing totals If the 4 20mA current is disconne...

Страница 4: ... then clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See section 5 17 Note Totalisation will continue until CLr no or CLr YE5 are displayed Resets the total display to zero when these two push buttons are operated simultaneously Selectable function in the ...

Страница 5: ...reset to zero by momentarily connecting the reset terminals RS1 and RS2 together with a resistance of less than 1kΩ as shown in Fig 2 Note The negative reset terminal RS2 is internally connected to the negative 4 20mA input terminal 3 The total display may also be reset to zero by operating the totalisers and push buttons simultaneously for more than two seconds See section 5 17 3 3 Remote flow in...

Страница 6: ...als 5 and 6 are internally joined and may be used for linking cable screens The Rate Totalisers earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosures are fitted with a bonding plate to ensure electrical continuity between the thr...

Страница 7: ...3 EMC The BA554E complies with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one point to the plants potential equalising conductor 7 ...

Страница 8: ...y be linearised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC block The rate display may then be calibrated using the CAL or 5Et functions to show the flow rate in the required linear engineering units Both the zero display at 4mA and the span display at 20mA are adjustable although for flow application the display at 4mA is usually zero...

Страница 9: ...be entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed If the code is incorrect or a button is not pressed within twenty seconds the Rate Totaliser will automatically return to the display mode Once within the configuration menu the required parameter c...

Страница 10: ... on or oFF See section 5 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 5 9 Display Summary of function CAL Calibration of the rate display using an external current source Enables the zero and span of the rate display to be adjusted using an external current source such as a calibrator When used with an accurate traceable calibrator this is the preferre...

Страница 11: ...and Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E and push buttons are operated simultaneously for more than 10 seconds See section 5 17 CodE Security code Defines a four digit numeric code that must be entered to gain access to the configuration me...

Страница 12: ...12 ...

Страница 13: ...earity with bi directional flow Use of the lineariser is described in section 6 of this instruction manual 5 5 Display resolution rE5n This function defines the resolution of the least significant display digit of the rate display Decreasing the display resolution can improve the readability of a noisy signal Select rE5n from the menu and press P which will reveal the current display resolution To...

Страница 14: ...ay and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required enter the setting and return to the conditioning menu by operating the E button 5 10 Calibration of the rate display using an external current source CAL This function enables the zero and span of the r...

Страница 15: ...as been activated see section 5 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr YES is displayed and then press P which will result in a 0000 prompt Using the and buttons and the P button to move to the next digit enter 5urE digit by digit to confirm the instruction Pressing E ...

Страница 16: ... the decimal point repeatedly operate the P button until the decimal point starts flashing The decimal point can then be positioned by pressing the or button When the required total scale factor has been set press E to enter the number and return to the 5CALE t prompt in the configuration menu 5 16 Clip off CLiP oFF To prevent totalisation of very low flow rates which over long periods may result ...

Страница 17: ...ay the existing security code with one digit flashing The flashing digit can be adjusted using the and push buttons when set as required operating the P button will transfer control to the next digit When all the digits have been adjusted press E to return to the CodE prompt in the configuration menu The revised security code will be activated when the Rate Totaliser is returned to the display mod...

Страница 18: ...Lineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct calibration from the variable to be displayed The number of break point required should first be entered using the Add and...

Страница 19: ...19 ...

Страница 20: ...ollowing break point 6 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the LtAb function described in section 6 19 each additional break point should be added before the highest existing breakpoint The first additional break point should be added before the default break po...

Страница 21: ...he E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starting point for the first break point 0 n where n is the total number of break points entered Press P and use the and buttons and the P button to move between digits to enter the required rate d...

Страница 22: ...her the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or button select 5td Press E to enter this selection and return to the FunC prompt in the configuration menu Step 4 Define function of P push button Select C P from the configuration menu and press P to rev...

Страница 23: ... the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1 000 litres in a cubic metre thus litres cubic metres 1 litre 1 1000 litres 5CALE t 1000 From the configuration menu select 5CALE t and press P to reveal the current five digit dividing factor Using ...

Страница 24: ...n and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates between 1 and 100 of maximum flow A security code of 1209 is required In the operating mode the BA554E is required to display the input current as a percentage of span when the P push button is operated ...

Страница 25: ...rminals 1 3 or terminals 3 12 if optional backlight is loop powered No power supply Confirm that a 4 20mA current is flowing in the loop Unstable rate display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Reduce resolution of the rate display to mask flow noise Unable to access configuration menu Incorrect security code Enter the correct security code ...

Страница 26: ...strument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 9 2 Alarms CAUTION These alarms outputs should not be used for critical safety applications such as an emergency shut down system The BA554E Rate Totaliser can be supplied with factory fitted dual alarms with sol...

Страница 27: ...sed and current will only flow in one direction Ron less than 5Ω 0 7V Roff greater than 1MΩ Fig 11 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switch any dc circuit with parameters equal to or less than V 40V I 200mA Fig 12 Typical alarm application Shown without recommended screened cables 27 ...

Страница 28: ...28 ...

Страница 29: ...ivated when the selected display rate or total equals the setpoint See section 9 2 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 2 6 no nC Normally open or normally closed output Sets the alarm output open or closed in the non alarm condition See section 9 2 7 H5tr Hysteresis Adjusts the alarm hysteresis Only available on rate alarms See section 9 2 8 dELA Alarm de...

Страница 30: ...by pressing the or button followed by the E button to return to the alarm menu 9 2 7 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm condition When deciding which is required care should be taken to ensure that the alarm output is fail safe as illustrated in Fig 10 no Alarm output open in non alarm condition nC Alarm output closed...

Страница 31: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs are activated by one variable the display alternates between the numerical value and Alr1 2 To enable or disable the function select FL5H from the alarm menu and press P which will reveal the current set...

Страница 32: ...n to the display mode Fig 14 Setpoint adjustment from the display mode To adjust an alarm setpoint select 5Px1 or 5Px2 and press P which will reveal the current setting Each digit of the setpoint may be adjusted using the and push buttons and the P button to move control to the next digit When the required setpoint has been entered pressing E will return the display to the 5Px1 or 5Px2 prompt from...

Страница 33: ...pply via an intrinsically safe interface as shown in Fig 17 Fig 17 Separately powered backlight When separately powered the backlight is a current sink drawing a constant current when the supply is equal to or greater the minimum specified voltage Below this supply voltage the backlight continues to function but with reduced brilliance Current Minimum voltage 35mA 11V 9 4 External keypad For appli...

Отзывы: