12

buttons simultaneously will exchange the
displays.

Note:

 Both decimal points must be

repositioned after the displays have been
exchanged.

5.7  Lower display:  ‘dISPLAY.2’

This function turns the lower display on or off.
When turned off, the BA544D will only have
one eight digit display which may be
programmed to show total flow or rate of flow.

To check the status of the lower display select
‘dISPLAY.2’ from the menu and press 

P

 which

will reveal if the function is ‘On’ or ‘OFF’.  The
settings may be changed by pressing the 

Up

 or

Down 

button followed by the 

E

 button to return

to the menu.

5.8  Rate scale factor:   ‘SCALE-r’

Together with the instrument timebase, this
function defines the arithmetic relationship
between the pulse input frequency and the rate
display.  When used with a flowmeter SCALE-r
should be set to the K-factor of the flowmeter
i.e.  the number of pulses the flowmeter
produces for a unit of flow.  e.g.  45.6 pulses
per litre.   See section 6 for a worked example.

SCALE-r is a dividing factor that may be
adjusted between 0.001 and 99999999.

To check or change the total scale factor select
'SCALE-r' from the main menu and press 

P

 to

reveal the existing setting, one digit will be
flashing.  The value of the flashing digit can be
changed by pressing the 

Up

 or 

Down

 buttons.

When this digit is correct pressing 

P

 will

transfer control to the next digit.

To position the decimal point in the rate scale
factor, move the flashing digit to the left hand
side of the required decimal point position and
simultaneously press the 

Up

 and 

Down

buttons.

When the required rate scale factor has been
entered, press 

E t

o store the number and

return to the main menu.

5.9  Timebase:  ‘t-bASE’

The timebase multiplies the rate display by 1,
60 or 3,600 depending upon whether the
BA544D is required to display rate per second,
per minute or per hour.    See Fig 6.

To  check  or  change  the  timebase,  select
't-bASE' from the main menu and press 

P

which will reveal the current setting.   Pressing
the 

Up

 or 

Down

 button will index through the

three options:

tb-1

for flow / second

tb-60

for flow / minute

tb-3600 

for flow / hour

Select the required multiplier and press 

E

 to

return to the main menu.

5.10  Rate filter:   ‘FILtEr’

This digital filter has two independent
adjustable parameters enabling the rate
display frequency response to be tailored for
optimum performance.

The filter parameters are controlled by a two
digit number.  The first digit defines the amount
of filtering applied to the display as shown
below.

First digit

Filter time constant

seconds

0X

              0

1X

              1.3

2X

              4.3

3X

              6.5

4X

              8.7

5X

            11.3

6X

            15.7

7X

            20.9

8X

            25.2

9X

            31.5

The second digit defines the deviation from the
displayed rate at which the filter will be
overridden and the rate display will move
rapidly to the new value.

Second

digit

Magnitude of step

change which will

produce a rapid

response

X0

              Off

X1

              1%

X2

              2%

X3

              4%

X4

              8%

X5

            12%

X6

            16%

X7

            24%

X8

            32%

X9

            64%

By careful adjustment of the two parameters a
stable display with an acceptable step input
response can be obtained for most
applications.

During commissioning it is recommend that
initially the second digit is set to 0 (off) and the
first digit is adjusted to provide acceptable rate

Содержание BA544D

Страница 1: ...Issue 3 7th April 2009 BA544D Battery powered pulse input field mounting rate totaliser Issue 3...

Страница 2: ...total 5 15 Security code 6 Calibration Example 6 1 Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenanc...

Страница 3: ...further extend the applications of this instrument The BA544D contains an internal replaceable battery that will power the instrument for up to five years Battery life depends upon how the BA544D is p...

Страница 4: ...ue to operate for about five hundred hours after the annunciator is activated but the exact time will depend upon how the instrument is programmed whether alarms are fitted and the input frequency Dur...

Страница 5: ...ater treatment installations Please consult BEKA associates if high vibration is anticipated The BA544D enclosure is surface mounting Accessory kits described in sections 8 4 8 5 of this manual enable...

Страница 6: ...one point Fig 4 Dimensions and terminal connections 4 4 Installing a replacement battery The internal battery will power the BA544D rate totaliser for about five years the exact time depends upon how...

Страница 7: ...by moving the slide switch to the left see Figs 3 4 c Remove the four D screws and lift off the front of the enclosure d Remove the two E screws securing the BA491 battery and gently pull the battery...

Страница 8: ...ond minute or hour Similarly to calculate the total flow in the required units of measurement the number of input pulses is divided by the total scale factor SCALE t Total flow is continuously added t...

Страница 9: ...9...

Страница 10: ...section 5 6 dISPLAY 2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relatio...

Страница 11: ...ype select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the four options UOLts Voltage pulse input Threshold 1V and 3V 10kHz max Inp...

Страница 12: ...int position and simultaneously press the Up and Down buttons When the required rate scale factor has been entered press E to store the number and return to the main menu 5 9 Timebase t bASE The timeb...

Страница 13: ...he total scale factor the total and grand total displays will be reset to zero To position the decimal point in the scale factor move the flashing digit to the left hand side of the required decimal p...

Страница 14: ...ed before access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a se...

Страница 15: ...Select the type of input Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off usi...

Страница 16: ...A544D is required to display 1 cubic metre for every 105 x 1 000 pulses received SCALE t should therefore be set to 105 000 Select SCALE t from the main menu and press P which will reveal the current...

Страница 17: ...rument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pres...

Страница 18: ...fter it has been functioning correctly the following table may help Symptom Cause Check No display Instrument has been switched OFF If BA544D has been switched OFF for extended period battery may need...

Страница 19: ...d not be used for critical safety applications such as a shut down system When the battery is exhausted both BA544D alarm outputs will open irrespective of whether normally open or normally closed out...

Страница 20: ...of alarm Defines whether the alarm operates on the rate or total display See section 8 2 4 SPr1 Alarm setpoint 1 or Adjusts the alarm setpoint The SPt1 alarm is activated when the rate or total displa...

Страница 21: ...rn to the alarm menu 8 2 4 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm selec...

Страница 22: ...s select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the re...

Страница 23: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Страница 24: ...mounting kits are available for securing the BA544D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Страница 25: ...Y 2 5 7 d P 5 6 EnbL 8 2 2 8 2 3 Fault finding during commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 2 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2...

Страница 26: ...t is switched on When a replacement battery is fitted or when the rate totaliser is turned on after not being used for an extended period the battery should be conditioned by drawing a relatively larg...

Отзывы: