BEKA BA537E Скачать руководство пользователя страница 16

5.7  Debounce:   

dEbouncE

dEbouncE

is an adjustable sub-menu in the

inPut

function

which

prevents

the

Rate

Totaliser

miscounting when the input pulse has noisy edges,
such as those resulting from a mechanical contact
closing and bouncing.

Three levels of protection

may be selected and the amount of debounce applied
depends upon the type of Rate Totaliser input that
has been selected in the 

inP

 

.

 

tYPE

 function.

The following table shows the minimum time that the
input pulse must be continuously above the upper
input switching threshold and continuously below the
lower switching threshold to ensure that the Rate
Totaliser processes the input pulse. Input switching
thresholds are shown in section 3.2.

De-bounce

level

Min input pulse width

Type of Input

Contact

All others

Default

1600µs

40µs

Heavy

3200µs

350µs

Light

400µs

5µs

The Rate Totalier’s maximum counting frequency
depends upon the debounce level selected, the shape
of the input pulse and its amplitude. The following
table assumes a square wave input and is only for
guidance. The maximum counting frequency will be
lower if the input pulses have sloping edges and the
pulse amplitude only slightly exceeds the input
switching thresholds.

ONLY FOR GUIDANCE

De-bounce

level

Max counting frequency

Type of input

Contact

All others

Default

250Hz

12kHz

Heavy

120Hz

2kHz

Light

1000Hz

100kHz

The minimum input frequency is 0.01Hz. Below this
frequency the rate display will be forced to zero.

The

dEbouncE

function is a sub-menu located in the

inPut

function.

Select

inPut

in the configuration

menu and press

(

which will reveal the

inP . tYPE

prompt, press the

&

or

*

button to select

dEbouncE

followed by

(

to reveal the existing setting.

Pressing the

&

or

*

button will scroll through the

three levels.

When the required level has been

selected, pressing

)

twice will enter the selection

and return the display to the

inPut

prompt in the

configuration menu.

5.8  Display update interval:   

uPdAtE

 

If either the rate or the total display is likely to
change rapidly, a longer interval between display
updates may simplify reading the Rate Totaliser
display. This function allows one of six different
display intervals between 0.5 and 5 seconds to be
selected. The selected display update interval does
not affect the update time of any other instrument
function.

To adjust the update interval select

uPdAtE

from the

configuration menu and press

(

to reveal the

existing time.

Pressing the

&

or

*

button will

scroll through the six times. When the required
interval has been selected press

)

to enter the

selection and return to the configuration menu.

5.9 Upper display:  

di5P-1

Usually total flow is shown on the larger upper eight
digit display, but this function allows rate to be
shown on the upper display and total on the smaller
lower display which can show six positive digits.

To check the status of the upper display, select

dI5P-1

from the configuration menu and press

(

which will reveal if the display is showing

rAtE

or

totAL

. The setting can be changed by pressing the

&

or

*

button followed by the

)

button to enter

the selection and return to the configuration menu.

5.10 Lower display:  

di5P-2

This function turns the lower display

on

or

off.

When

turned

off

, the BA537E or the BA538E will only have

one eight digit display which may be configured in
the 

di5P-1

 function to show total flow or rate of flow.

To check the status of the lower display, select

di5P-2

from the configuration menu and press

(

to

reveal if the lower display is

on

or

oFF

. The setting

may be changed by pressing the

&

or

*

button

followed by the

)

button to enter the selection and

return to the configuration menu.

16

Содержание BA537E

Страница 1: ...Issue 5 9th July 2019 BA537E and BA538E One input General Purpose pulse input Rate Totalisers Issue 5...

Страница 2: ...s 6 3 Add a segment add 6 4 Remove a segment del 6 5 Input frequency pul5efre 6 6 K factors l factor 6 7 Lineariser error messages 7 Configuration example 7 1 Configuration procedure 8 Maintenance 8 1...

Страница 3: ...E and BA538E have a single pair of input terminals for connection to all types of transducer When counting pulses from a transducer requiring energising such as a switch contact open collector or a tw...

Страница 4: ...ts when the Rate Totaliser is fitted with optional alarms and the AC5P setpoints function has been enabled See 9 4 13 Access to configuration menu 2 3 Displays The BA537E and BA538E have two digital d...

Страница 5: ...eshold Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Magnetic pick off 0mV 40mV peak Proximity detector 1 2mA 2 1mA...

Страница 6: ...configuration menu VoLt5 L and VoLt5 H as shown in section 3 2 The Rate Totalisers contain a configurable debounce circuit to prevent false triggering of the instrument Three levels of de bounce prote...

Страница 7: ...o prevent vibration damage Note Optional backlight is internally powered Fig 3A BA537E dimensions terminals Cut out dimensions Recommended for all installations Mandatory to achieve an IP66 seal betwe...

Страница 8: ...ing is supported Fig 4 Fitting panel mounting clamps 4 4 Scale card The Rate Totaliser s units of measurement are shown on a printed scale card in a window at the right hand side of the display The sc...

Страница 9: ...configured totalisation continues so that any flow occurring during this time is recorded 5 1 Configuration structure Fig 6 shows the BA537E and BA538E calibration structure The rate and total displa...

Страница 10: ...figuration menu is shown diagrammatically in Fig 7 When returning to the totalisation mode following reconfiguration the Rate Totaliser will display dAtA followed by 5AVE while the new information is...

Страница 11: ...of litres in 1 000 imperial gallons 5CALE t may be adjusted between 0 0001 and 99999 The total flow display is independent of the rate display See section 5 13 Display Summary of function 5CALE r Rat...

Страница 12: ...tored See section 5 20 Display Summary of function CLr Gtot Reset grand total from configuration menu This function resets the grand total to zero from within the configuration menu when CLr YE5 is se...

Страница 13: ...dEbounCE which configure the Rate Totaliser input and input noise rejection 5 6 Input type inP tYPE inP tYPE is a sub menu in the inPut function which defines the type of flowmeter or input pulse that...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...on will scroll through the three levels When the required level has been selected pressing twice will enter the selection and return the display to the inPut prompt in the configuration menu 5 8 Displ...

Страница 17: ...control to the decimal point that may be positioned between any of the digits or may be omitted by moving it to the right of the least significant digit When set as required press to return to the FAC...

Страница 18: ...play stability and a fast response to a large rate signal change To check or change the filter select FiLtEr in the configuration menu and press which will reveal the existing settings with the first...

Страница 19: ...ge the setting followed by the button twice to enter the change and return to the LoC clr prompt in the configuration menu 5 21 Grand total reset from configuration menu Clr Gtot The grand total is a...

Страница 20: ...from the configuration menu and press which will result in a 0000 display with the first digit flashing This is a request to confirm the reset to factory default instruction by entering 5urE Using th...

Страница 21: ...ibration certificate specifying the average K factor and the flow range over which it applies For use over extended flow ranges and for non linear devices multiple K factors will be specified often in...

Страница 22: ...22...

Страница 23: ...of four sub functions If Add is not displayed repeatedly press the or button to select Add followed by which will cause the current segment and the total number of lineariser segments to be displayed...

Страница 24: ...s divided by L FACtor which is adjustable between 0 0001 and 99999 for flow applications it should be set to the K factor of the flowmeter K factor is the number of pulses that the flowmeter produces...

Страница 25: ...ction If the Rate Totaliser is subsequently found to miscount the noise rejection can be increased Enter the selection and return to the inPut prompt in the configuration menu by pressing the button t...

Страница 26: ...o be displayed in the required engineering units The rate display timebase is determined by t bA5E that is adjusted in Step 11 In this example the rate of flow display is required in imperial gallons...

Страница 27: ...eveal the sub menu Again using the or button select the local total reset function clr tot and press This function is required so using the or button select on followed by to return to the clr tot pro...

Страница 28: ...Alarms have been disabled following calibration change Re enable both alarms 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA537E or a BA538E fails after i...

Страница 29: ...ory fitted backlight that produce green illumination enhancing display contrast and enabling it to be read at night or in poor lighting conditions Both the BA537E and BA538E backlights are internally...

Страница 30: ...hat total alarms do not have hysteresis Alarm AL2 is identical to alarm AL1 The following table summarises each of the alarm configuration functions and includes a cross reference to more detailed inf...

Страница 31: ...push button will toggle the selection between rAtE and totAL when set as required press the button to return to the alarm sub menu Note When tYPE is changed the alarm configuration is automatically re...

Страница 32: ...32...

Страница 33: ...ss to enter the value and return to the dELA prompt in the alarm sub menu The Rate Totaliser s alarm annunciator will start flashing immediately an alarm condition occurs and will continue for the del...

Страница 34: ...ained by operating the and push buttons simultaneously as shown in Fig 16 If the setpoints are not protected by a security code the alarm setpoint prompt 5P1r or 5P1t will be displayed depending upon...

Страница 35: ...tor closes P2 is connected to P1 and a pulse output current flows through the resistor R1 The current flowing in the circuit is determined by resistor R1 which should be chosen to limit the output cur...

Страница 36: ...the output pulse 1 10 100 1000 10000 Using the or push button select diVidE in the pulse output sub menu and press which will reveal the existing divisor The selected divisor can be changed by pressin...

Страница 37: ...ut to be controlled by the rate or the total display and to be scaled Fig 17 4 20mA output configuration sub menu 9 6 3 4 20mA output 4 20 oP Access the Rate Totaliser s configuration menu as describe...

Страница 38: ...t 20 000 in the 4 20mA output sub menu and press which will reveal the existing rate or total display with one digit flashing The required display can be entered using the or push button to adjust the...

Отзывы: