4
2.3 Displays
The BA534D has two digital displays and
associated annunciators, plus a flow indicator as
shown on page 1.
Rate
Shows the flow rate on the
Display
smaller six digit display.
Total
Shows the total flow on the
display
larger eight digit display. Set to
zero when local or remote reset
switch is operated.
Flow
This disc in the lower left
indicator
hand corner of the display
‘rotates’ for two seconds each
time an input pulse is received.
Therefore when the pulse input
frequency exceeds 0.5Hz the disc
appears to rotate continuously.
Hold
Activated when the input
Annunciator
frequency
is below the clip-off
threshold.
Reset
Activated when the total
Annunciator
display
is being reset.
3. SYSTEM DESIGN
3.1
Flow transmitter loops
The BA534D may be connected to almost any
pulse output flowmeter and calibrated to display
rate of flow and total flow in the same or different
engineering units.
Fig 2 illustrates the basic circuit that is used for all
BA534D installations. For simplicity, connections
for the optional pulse output, 4/20mA output and
backlight are included in section 8 of this manual.
Fig 2 BA534D in flow application
When designing a system it is important to
remember that terminals 2, 4, 6 and 8 are
interconnected within the BA534D - see Fig 1.
3.2 Power supply
The BA534D may be powered from any dc supply
having an output voltage between 10 and 30V.
The instrument consumes about 12mA rising to
15mA when a proximity detector input is used.