.2.5  Setpoint adjustment:   ‘SPx1’ and

                                                 ‘SPx2’

The rate alarm setpoints SPr1 and SPr2 may be
positioned anywhere between 0 and 999999, and
the total alarm setpoint SPt1 and SPt2 anywhere
between 00000000 and 99999999.

To adjust the setpoint of alarm 1 select 'SPr1' or
‘SPt1’, depending upon how it has been
programmed, from the alarm menu. Press 

P

 which

will reveal the existing value with one digit
flashing.  Each digit of the setpoint can be
adjusted using the 

Up

 and 

Down

 push-buttons,

and the 

P

 button to move to the next digit.  The

position of the decimal point is defined by the d.P.
function in the main menu which should be
adjusted first.  When the required value has been
entered press 

 to return to the alarm menu.

Note:

 ‘SPr1’ is displayed when alarm 1 has been

programmed as a rate alarm and ‘SPt1’ when
programmed as a total alarm.

8.2.6  Alarm function:   ‘HI.LO’

Each alarm must be conditioned as a high or low
alarm.   To check or change the alarm function
select 'HI.LO' from the alarm menu and press 

P

 to

reveal the current setting.  The function can be
changed by pressing the 

Up

 or 

Down

 buttons

followed by the 

E

 button to return to the alarm

menu.

8.2.7  Alarm output status:   ‘no.nc’

The two alarm outputs may be open or closed in
the non-alarm condition.  When the BA534D
power supply is turned off or disconnected, both
the alarm outputs will open irrespective of whether
normally open or normally closed outputs have
been selected.  Therefore, when designing an
alarm system normally closed ‘nc’ should be
selected so that the output opens when an alarrm
occurs or if the power supply fails.

To check the alarm output status select 'no.nc'
from the alarm menu and press 

P

 to reveal the

current setting.  The function can be changed by
pressing the 

Up

 or 

Down

 button followed by the 

E

button to return to the alarm menu.

8.2.8  Hysteresis:   ‘HStr’

Hysteresis is only available on rate alarms.
During programming hysteresis is shown in the
units of rate the BA534D has been calibrated to
display.

To adjust the hysteresis, select 'HStr' from the
alarm menu and press 

P

 which will reveal the

existing figure.  Each digit can be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

 button

to move to the next digit.  When the required
hysteresis has been entered, press 

to return to

the alarm menu.

e.g.  A BA534D calibrated to display a flow of 0 to
5000, with a high alarm set at 4000 and hysteresis
of 100 will perform as follows:

High alarm will be activated when flow
equals or exceeds 4000, but will not reset
until the flow falls below 3900.

8.2.9  Alarm delay:   ‘dELA’

This function enables activation of the alarm
output to be delayed for a fixed time following the
alarm condition occurring.  The delay can be
programmed in 1 second increments up to 3600
seconds.  If a delay is not required zero should be
entered.  To adjust the delay select 'dELA' from
the alarm menu and press 

P

 which will reveal the

existing delay time.  Each digit of the delay can be
adjusted using the 

Up

 and 

Down

 push-buttons,

and the 

P

  button to move to the next digit.  When

the required delay has been entered, press 

to

return to the alarm menu.

The alarm annunciator will start flashing
immediately an alarm occurs and continue for the
delay time after which the alarm output will be
activated.

8.2.10  Alarm silence time:   ‘SIL’

The alarm silence function is primarily intended for
use in small installations where the alarm output
directly operates an annunciator such as a
sounder.  When the alarm silence time is set to
any figure other than zero, the 

P

 push-button

becomes an alarm accept button.

After an alarm has occurred, operating the 

P

button will cause the alarm output to revert to the
non-alarm condition for the programmed alarm
silence time.  When an alarm is silenced the alarm
annunciator will flash until the silence time
expires.

To adjust the silence time select 'SIL' from the
alarm menu and press 

P

  which will reveal the

existing time.  The time may be adjusted to
between 0 and 3600 seconds in 1 second
increments.  Each digit can be adjusted using the

Up

 and 

Down

 push-buttons, and the 

P

  button

transfers control to the next digit.  When the
required time has been entered press 

to return

to the alarm menu.

Содержание BA534D

Страница 1: ...Issue 10 18th September 2008 BA534D Externally powered pulse input field mounting rate totaliser issue 10...

Страница 2: ...Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessorie...

Страница 3: ...ys further extend the applications Fig 1 Simplified block diagram of BA534D 2 1 Initalisation Each time power is applied to the instrument initalisation is performed After a short delay the following...

Страница 4: ...et Activated when the total Annunciator display is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA534D may be connected to almost any pulse output flowmeter and calibrated to display rat...

Страница 5: ...4D rate totaliser is housed in a robust IP66 glass reinforced polyester GRP enclosure incorporating an armoured glass window and stainless steel fittings It is suitable for exterior mounting in most i...

Страница 6: ...rective 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs and the BA534D earth terminal should be locally earthed or connected to an earthed cable screen To prevent ci...

Страница 7: ...total scale factor SCALE t Total flow is continuously added to the grand total The BA534D displays real decimal points Moving the position of a decimal point in a scale factor will therefore affect th...

Страница 8: ...8...

Страница 9: ...2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the p...

Страница 10: ...s from a wide variety of sensors To define an input type select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the five options UOLts...

Страница 11: ...igit can be changed by pressing the Up or Down buttons When this digit is correct pressing P will transfer control to the next digit To position the decimal point in the rate scale factor move the fla...

Страница 12: ...r control to the next digit To position the decimal point in the scaling factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and...

Страница 13: ...git of the code can be changed using the Up and Down push buttons and the P button to move to the next digit When the required code has been entered press E to return to the main menu The revised secu...

Страница 14: ...ush button until the third least significant digit of the total display and following decimal point are flashing This gives the required total display resolution of 0 01 Press P to move control to the...

Страница 15: ...enter 1050000 Finally return to the SCALE t prompt in the main menu by pressing E Step 9 Define clip off In this example totalisation is to be inhibited at flow rates below 300 litres per hour Select...

Страница 16: ...ode 1209 digit by digit The P button will transfer control between digits When the new code has been entered press E to return to the main programme menu Step 13 Return to the display mode Following c...

Страница 17: ...20mA output calibration Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING M...

Страница 18: ...utputs WARNING These alarm outputs should not be used for critical safety applications such as a shut down system When the BA534D power supply is turned off or disconnected both BA534D alarm outputs w...

Страница 19: ...19 Fig 10 Alarm menu structure...

Страница 20: ...available on rate alarms See section 8 2 8 Summary of programmable alarm functions dELA Alarm delay time Adjusts the delay between the display equalling the setpoint and the alarm output being activa...

Страница 21: ...st the hysteresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next d...

Страница 22: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 2 12 Adjusting alarm setpoints from th...

Страница 23: ...pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA534D display changes A programmable divider enables the puls...

Страница 24: ...ng digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the next digit When the flow rate corresponding to an output current o...

Страница 25: ...mounting kits are available for securing the BA534D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Страница 26: ...ng commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 2 clear 5 14 Guarantee 7 5 HI LO 8 2 2 8 2 6 HStr 8 2 2 8 2 8 InPut 5 5 Installation 4 Instrument identificati...

Отзывы: