3.  INTRINSIC SAFETY CERTIFICATION
3.1 ATEX certificate

The BA488CF-P has been issued with EC-Type
Examination Certificate by Notified Body  Intertek
Testing Services (ITS) confirming compliance with
the European ATEX Directive 94/9/EC for Group II,
Category 1, gas atmospheres, EEx ia IIC T4.  The
instrument bears the Community Mark and, subject
to local codes of practice, may be installed in any
of the European Economic Area (EEA) member
countries.  ATEX certificates are also acceptable
for installations in Switzerland. This manual
describes installations which conform with
EN 60079: Part 14 Electrical Installation in
Hazardous Areas.  When designing systems for
installation outside the UK, the local Code of
Practice should be consulted. Some of the
standards specified may have subsequently been
deharmonised, please see BEKA Declaration of
Conformity for current conformity.

3.2  Zones, gas groups and T rating

The BA488CF-P has been issued with EC Type
Examination certificate ITS04ATEX22779
confirming that it complies with the requirements
for Group II Category 1 G Ex ia IIC T4 (Tamb –40
to 60°C) specified in the ATEX Directive.  When
connected to a suitable system the BA488CF-P
may be installed in:

Zone 0

explosive gas air mixture
continuously present.

Zone 1

explosive gas air mixture
likely to occur in normal
operation.

Zone 2 explosive gas air mixture not

likely to occur, and if it does will
only exist for a short time.

Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450°C

T2

300°C

T3

200°C

T4

135°C

At an ambient temperature between –40 and
+60°C.

Note

: the guaranteed operating temperature range

of the Fieldbus Display is –20 to +60°C

This allows the BA488CF-P to be installed in all
Zones and to be used with most common industrial
gases.

WARNING installation in Zone 0

When installed in a Zone 0 potentially
explosive atmosphere requiring apparatus
of Category 1G, the fieldbus display shall be
installed such that even in the event of rare
incidents, an ignition source due to impact
or friction between the aluminium enclosure
at the rear of the instrument mounting panel
and iron/steel is excluded.

3.3   Fieldbus connection

The BA488CF-P PROFIBUS display is powered
and communicates via the fieldbus, which is
connected to terminals 1 and 2.  These terminals
comply with the Fieldbus Intrinsically Safe Concept
(FISCO) defined in EN 60079 Part 27, which
simplifies intrinsic safety system design.

The BA488CF-P may also be connected to non
FISCO compliant fieldbus segments by using the
entity concept to assess safety.

Terminals 1 and 2 of the BA488CF-P Fieldbus
Display are not polarised and have the following
safety parameters:

Ui

=

17.5V dc

Ii

=

380mA dc

Pi

=

5.32W

For non FISCO compliant segments, the safety
parameters of the power supply or isolator
powering the fieldbus segment must be equal to or
less than these figures.

The maximum equivalent capacitance and
inductance at terminals 1 & 2 of the BA488CF-P
Fieldbus Display are:

Ci

=        1nF

Li

=       8µH

To determine cable parameters for non FISCO
compliant segments, the sum of Ci and Li of all the
field devices should be subtracted from the
maximum cable parameters permitted by the
device powering the fieldbus segment.

3.4

  

External switches

For applications requiring operator inputs to be
made by large industrial push buttons, terminals
S1 to S7 facilitate external switches to be
connected to the Fieldbus Display.   When external
switches are connected, the BA488CF-P may be
configured so that the front panel push buttons
continue to function or are disabled.

Terminals S1 to S7 have the following combined
output safety parameters:

Содержание BA488CF-P PROFIBUS PA

Страница 1: ...Issue 3 8th December 2011 BA488CF P PROFIBUS PA Intrinsically safe Panel mounting Fieldbus Display issue 3...

Страница 2: ...3 4 Units 6 3 5 Alarms 6 3 5 1 Alarm Summary 6 3 5 2 Alarm Activation 6 3 5 3 Alarm Output 6 3 6 Display 6 3 6 1 Settings 6 3 6 2 Quick Access 6 3 6 3 Access Code 6 3 6 4 Status Text 6 3 6 5 Last Inpu...

Страница 3: ...ieldbus variable and are configured via the instrument menus and push buttons They can not be controlled via the fieldbus The instrument has been certified intrinsically safe by European Notified Body...

Страница 4: ...roll through the display screens by operating the or push buttons The number of screens available depends upon how the BA488CF P PROFIBUS display has been configured and the number of process variable...

Страница 5: ...BA488CF P to be installed in all Zones and to be used with most common industrial gases WARNING installation in Zone 0 When installed in a Zone 0 potentially explosive atmosphere requiring apparatus o...

Страница 6: ...tion 5 7 of EN 60079 11 This allows each of the BA488CF P alarm outputs to be connected to any intrinsically safe circuit protected by a certified Zener barrier or galvanic isolator providing that the...

Страница 7: ...apparatus i e the switch must be mechanically activated and have IP20 protection and both the switch and the wiring must be capable of withstanding a 500V rms insulation test to earth for one minute...

Страница 8: ...d and the instrument secured with four panel mounting clips The BA488CF P liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrume...

Страница 9: ...es with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected to the potential equalising network...

Страница 10: ...tered Using the or button adjust the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits hav...

Страница 11: ...onfiguration at the fieldbus system host see the PROFIBUS Fieldbus Interface Guide which may be downloaded from the BEKA website This sub menu allows one of eleven standard display formats to be selec...

Страница 12: ...ic characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the and push buttons Numbers upper lower case lette...

Страница 13: ...light brilliance and display contrast are adjustable from this sub menu 6 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is described in sections 2 1 and 6 4 When enabled an oper...

Страница 14: ...display will be terminated 6 3 11 Instrument address Enables the required three digit PROFIBUS address to be entered digit by digit using the instrument s push buttons 6 4 Quick Access Menu The Quick...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...3 2 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certifie...

Страница 18: ...ber on the rear panel This tag number is not visible from the front of the instrument after installation 8 2 PROFIBUS Interface Guides The BEKA PROFIBUS Interface Guide which may be downloaded from th...

Страница 19: ...eldbus Connection 3 3 Interface Guide 8 2 FISCO 3 3 4 1 FOUNDATION fieldbus 1 0 FM Approval Appendix 1 Gas groups 3 2 Appendix 1 2 Guarantee 7 5 IECEx Certification Appendix 2 Input Scaling 6 3 2 Inst...

Страница 20: ...P comply with the requirements for a FISCO Field Device specified in IEC60079 27 The intrinsically safe circuits shown in Figs 2 and 3 of this manual may therefore be used for installations in the USA...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...28...

Страница 29: ...the following certification code and marking For gas Ex ia IIC T4 Ta 40 C to 60 C The specified intrinsic safety parameters are identical to the ATEX parameters and confirm that terminals 1 2 comply w...

Отзывы: