APPENDIX 1
FM approval for use in USA

A1.0  Factory Mutual Approval

For installations in the USA, the BA488CF-P and
optional alarms have been approved intrinsically
safe and nonincendive by FM Approvals, project
identification 3022546. Copies of the Certificate of
Compliance are available from BEKA associates.

A1.1  Intrinsic safety  approval

The BA488CF-P is approved to the FM Class 3610
intrinsic safety standard for use in indoor
hazardous (classified) locations.  Installations must
comply with BEKA associates Control Drawing
CI480-17, which is attached to this Appendix,
ANSI/ISA RP12.06.01 ‘Installation of Intrinsically
Safe Systems for Hazardous (Classified)
Locations’ and with the National Electrical Code
ANSI/NFPA70.

The BA488CF-P has a T4 rating at ambient
temperatures up to +60

o

C and may be used with

the following gases and dusts:

Intrinsic Safety

Division 1 or 2

Class I    Group A & B
               Group C
               Group D

Zone 0, 1 or 2
Class 1   Group IIC
               Group IIB
               Group IIA

The FM entity parameters are identical to the
ATEX parameters and, like the ATEX certification,
confirm that terminals 1 & 2 of the BA488CF-P
comply with the requirements for a FISCO Field
Device specified in IEC60079-27.  The intrinsically
safe circuits shown in Figs 2 and 3 of this manual
may therefore be used for installations in the USA,
providing the fieldbus power supply, terminators,
Zener barriers and galvanic isolators are FM
Approved and comply with BEKA associates
Control Drawing CI480-17.  The FM Approval also
allows the BA488CF-P to be connected to non-
FISCO systems using the entity concept – see
section 4.2 of this manual.

A1.2  Nonincendive approval

The BA488CF-P is Class 3611 nonincendive
approved by Factory Mutual allowing it to be
installed in Division 2 indoor hazardous (classified)
locations without the need for Zener barriers or
galvanic isolators.   Installations must comply with
the BEKA associates Control Drawing CI480-18,
which is attached to this Appendix, and with the
National Electrical Code ANSI/NFPA70.

The FM Nonincendive Approval also allows the
instrument to be connected to any FNICO
compliant fieldbus segment powered by FM
Approved Associated Nonincendive Field Wiring
Apparatus.

The BA488CF-P has a T4 rating at ambient
temperatures up to +60

o

C and may be used with

the following gases and dusts:

Nonincendive

Division 2

Class I    Group A & B
               Group C
               Group D

Zone 2
Class I    Group IIC
               Group IIB
               Group IIA

Содержание BA488CF-P PROFIBUS PA

Страница 1: ...Issue 3 8th December 2011 BA488CF P PROFIBUS PA Intrinsically safe Panel mounting Fieldbus Display issue 3...

Страница 2: ...3 4 Units 6 3 5 Alarms 6 3 5 1 Alarm Summary 6 3 5 2 Alarm Activation 6 3 5 3 Alarm Output 6 3 6 Display 6 3 6 1 Settings 6 3 6 2 Quick Access 6 3 6 3 Access Code 6 3 6 4 Status Text 6 3 6 5 Last Inpu...

Страница 3: ...ieldbus variable and are configured via the instrument menus and push buttons They can not be controlled via the fieldbus The instrument has been certified intrinsically safe by European Notified Body...

Страница 4: ...roll through the display screens by operating the or push buttons The number of screens available depends upon how the BA488CF P PROFIBUS display has been configured and the number of process variable...

Страница 5: ...BA488CF P to be installed in all Zones and to be used with most common industrial gases WARNING installation in Zone 0 When installed in a Zone 0 potentially explosive atmosphere requiring apparatus o...

Страница 6: ...tion 5 7 of EN 60079 11 This allows each of the BA488CF P alarm outputs to be connected to any intrinsically safe circuit protected by a certified Zener barrier or galvanic isolator providing that the...

Страница 7: ...apparatus i e the switch must be mechanically activated and have IP20 protection and both the switch and the wiring must be capable of withstanding a 500V rms insulation test to earth for one minute...

Страница 8: ...d and the instrument secured with four panel mounting clips The BA488CF P liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrume...

Страница 9: ...es with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected to the potential equalising network...

Страница 10: ...tered Using the or button adjust the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits hav...

Страница 11: ...onfiguration at the fieldbus system host see the PROFIBUS Fieldbus Interface Guide which may be downloaded from the BEKA website This sub menu allows one of eleven standard display formats to be selec...

Страница 12: ...ic characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the and push buttons Numbers upper lower case lette...

Страница 13: ...light brilliance and display contrast are adjustable from this sub menu 6 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is described in sections 2 1 and 6 4 When enabled an oper...

Страница 14: ...display will be terminated 6 3 11 Instrument address Enables the required three digit PROFIBUS address to be entered digit by digit using the instrument s push buttons 6 4 Quick Access Menu The Quick...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...3 2 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certifie...

Страница 18: ...ber on the rear panel This tag number is not visible from the front of the instrument after installation 8 2 PROFIBUS Interface Guides The BEKA PROFIBUS Interface Guide which may be downloaded from th...

Страница 19: ...eldbus Connection 3 3 Interface Guide 8 2 FISCO 3 3 4 1 FOUNDATION fieldbus 1 0 FM Approval Appendix 1 Gas groups 3 2 Appendix 1 2 Guarantee 7 5 IECEx Certification Appendix 2 Input Scaling 6 3 2 Inst...

Страница 20: ...P comply with the requirements for a FISCO Field Device specified in IEC60079 27 The intrinsically safe circuits shown in Figs 2 and 3 of this manual may therefore be used for installations in the USA...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...28...

Страница 29: ...the following certification code and marking For gas Ex ia IIC T4 Ta 40 C to 60 C The specified intrinsic safety parameters are identical to the ATEX parameters and confirm that terminals 1 2 comply w...

Отзывы: