BEKA BA474D Скачать руководство пользователя страница 23

21

8.   CONFIGURATION EXAMPLE

In this example a BA474D indicating temperature
transmitter is required to display temperature in
degrees Celsius with maximum resolution. The
temperature sensor is a 3 wire Pt100 resistance
thermometer and the 4/20mA transmitter output is
required to representing –10 to +250

o

C. .  A left hand

justified bargraph  representing 100.0 to 200.0

o

C is

required. Resistance thermometer failure is to be
indicated by an overrange output current of 21.0mA.
After configuration access to the configuration menu
is to be protected by code 1209.

Configuration is performed using the four push
buttons which are located behind the removable
switch cover below the digital display – see Fig 7.
The BA474D can be supplied with factory fitted
external push buttons if frequent adjustments are
required.

The transmitter configuration may also be
performed via HART

 

communication from a local

or remote configurator.  The HART

 

communication

protocol  includes additional functions allowing the
complete temperature loop, including the
temperature sensor and the transmitter load, to be
calibrated  - See the BEKA HART

 Interface Guide

which may be downloaded from
www.beka.co.uk/manuals

Step 

1

Access the configuration menu &
select the type of input.

See: Fig 9 and section 7.2.1
New BA474D indicating temperature
transmitters are supplied conditioned
with default access code ‘0000’ that
allows unrestricted access to the
configuration menu.

To enter the configuration menu press
buttons 

P

 and 

E

 simultaneously which

will cause the first prompt ‘InPut’ to be
displayed.   Press 

P

 to enter the function

and the transmitter will display the
current type of input.   To configure the
transmitter to operate with a three wire
resistance thermometer press the 

 or

 button until ‘3rtd’ is displayed.  When

selected press 

E

 to enter the selection

and return to the ‘InPut’ prompt in the
configuration menu.

Step 2

Select resistance thermometer type

See:  Fig 9 and section 7.2.10
Using the 

 or 

 button select the

‘r,tYPE’ prompt from the configuration
menu and press 

P

 to enter the function

which enables the type of resistance
thermometer to be selected. The
transmitter will display the existing type

of resistance thermometer, using the 

or 

 button select ‘100r’ which is the

required Pt100 sensor. Enter the
selection by pressing the 

E

 button that

will return the display to the ‘r.tYPE’
prompt in the configuration menu.

Step 3

Select units of digital display

See: Fig 9 and section 7.2.3
Using the 

 or 

 button select ‘dEG’

from the configuration menu and press 

P

to enter the function which enables the
digital display units of measurement to
be selected. Using the 

 or 

 button

scroll through the options and select ‘ºC’
which represents degrees Celsius.
Press 

E

 to enter the selection and return

the transmitter display to the ‘dEG’
prompt in the configuration menu.

Step 4

Select display resolution

See: Fig 9 and section 7.2.4
Using the 

 or 

 button select ‘rESn’

from the configuration menu and press 

P

to enter the function which determines
the resolution of the digital display.
Using the 

 or 

 button select ‘hi’ to

provide the required 0.1 resolution
display.  Press 

E

 to enter this selection

and return the display to the ‘rESn’
prompt in the configuration menu.

Step 5

Sensor fault detection

See: Fig 9 and section 7.2.6
Using the 

 or 

 button select ‘FAuLt’,

the input sensor fault detection function,
from the configuration menu and press

P

.  Using the 

 or 

 button scroll

through the options and select ‘uP 21’
which forces the output current to
21.0mA when a sensor failure is
detected.   Enter the selection by
pressing 

E

 which will also return the

transmitter display to the ‘FAuLt’ prompt
in the configuration menu.

Step 6

Configuration of 4/20mA output

See: Fig 9 and section 7.2.7
The BA474D transmitter input at which
the transmitter output current is 4mA
and 20mA is defined by the ‘CAL’
function which contains two sub-
functions.
Using the 

 or 

 button select ‘CAL’

from the configuration menu and press 

P

which will show the ‘ZEro’ sub-function
prompt.  Press 

P

 again to enter this sub-

function, which will reveal the existing
input at which the transmitter output
current is 4mA.   Adjust the display to
the required –0010.0 using the 

 or 

button to adjust the flashing digit and the

Содержание BA474D

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA474D...

Страница 2: ...Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0...

Страница 3: ...Issue 8 4 th March 2014 BA474D Intrinsically safe field mounting indicating temperature transmitter Issue 8...

Страница 4: ...play bAr 7 2 9 Access code CodE 7 2 10 Resistance thermometer type r tYPE 7 2 11 Decimal point position dP 7 2 12 Lower input display in Lo 7 2 13 Higher input display in Hi 7 3 Default configuration...

Страница 5: ...ned in Appendices to this manual The transmitter is HART Registered and is compliant with HART protocol standard revision 7 HART commissioning information is included in the BA47X 67X Indicating Tempe...

Страница 6: ...endix 1 which describes ATEX installations complying with EN 61241 14 Dust certification is an option that must be specified when the transmitter is ordered 4 2 Zones gas groups and T rating The BA474...

Страница 7: ...6 The BA474D Indicating Temperature Transmitter is loop powered via these terminals which have the following input safety parameters Ui 28V Ii 200mA Pi 0 85W When installed in a hazardous area the tr...

Страница 8: ...perate multiple loops the negative side of the supply is normally earthed To also allow the negative side of the 4 20mA load to be earthed it is necessary to have a Zener barrier in each of the two wi...

Страница 9: ...e it must be transparent to HART signals 5 2 Use as associated apparatus WARNING When used as associated apparatus without Zener barriers or galvanic isolators the BA474D transmitter must be installed...

Страница 10: ...zardous area the same Zener barriers or galvanic isolators required for transmitter operation are required When installed in a safe area as associated apparatus the supply terminals 5 6 may be directl...

Страница 11: ...n the three conduit cable entries The BA474D liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument Without a backlight there...

Страница 12: ...eparates the intrinsically safe and non intrinsically safe terminals within the enclosure Conductors of intrinsically safe circuits and non intrinsically safe circuits should not be contained in the s...

Страница 13: ...protected by an access code the first parameter InPut will be displayed If the transmitter is protected by an access code CodE will be displayed first Pressing P will allow the four digit security co...

Страница 14: ...or high display resolution See section 7 2 4 Transmitter Summary display of function FAuLt Sensor fault analogue indication Selects 1 of 3 under over range output currents to indicate that a sensor fa...

Страница 15: ...rmocouple has been selected press E to enter the selection and return to the t tYPE prompt in the configuration menu 7 2 3 Units of digital display dEG The transmitter digital display may be in one of...

Страница 16: ...ss P which will display the ZEro function in the sub menu pressing P again will reveal the existing transmitter input at which the transmitter output current is 4mA Input is shown in units which depen...

Страница 17: ...P button again will return control to one of the digits 7 2 9 Access code for configuration menu CodE Access to the configuration menu may be protected by a four digit security code which must be ent...

Страница 18: ...oned using either the or button Pressing the P button again will return control to one of the digits 7 2 13 Higher input display in Hi This function which only appears in the menu when the transmitter...

Страница 19: ...17...

Страница 20: ...18...

Страница 21: ...19...

Страница 22: ...on site Function Factory default Transmitter input InPut 3 wire RTD Sensor type t tYPE Pt100 Units of digital display dEG C Display resolution rESn Low Sensor fault FAuLt Off 4 20mA output CAL 0 0 to...

Страница 23: ...configuration menu and press P to enter the function which enables the type of resistance thermometer to be selected The transmitter will display the existing type of resistance thermometer using the...

Страница 24: ...ArLo sub function may be selected Press P to enter the bArLo sub function which will reveal the existing digital display at which the bargraph starts Set the display to 0100 0 using the or button to a...

Страница 25: ...een activated Sensor and input wiring 9 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Use as an intrinsically safe transmitter Live maintenance is permitted on in...

Страница 26: ...a scale for the horizontal bargraph Alternatively information may be added on site via an embossed strip dry transfer or a permanent marker To gain access to the display escutcheon remove the terminal...

Страница 27: ...r than 180k Note Because of the series protection diodes some test meters may not detect a closed alarm output Fig 12 Equivalent circuit of each alarm output WARNING Connection of alarm output to a su...

Страница 28: ...ions Display Description of function ALr1 Alarm 1 ALr2 Alarm 2 The two functions each contain seven identical sub functions one set for configuration alarm 1 and the other for configuration alarm 2 Se...

Страница 29: ...27...

Страница 30: ...o reveal the current setting The function may be changed by pressing the or button pressing the E button will enter the setting and return the display to the Hi Lo prompt in the alarm menu 10 4 8 Alar...

Страница 31: ...xists the alarm will be reactivated 10 4 12 Access Setpoint ACSP This function controls a separate menu that provides direct access to the alarm setpoints when the BA474D transmitter is in the operati...

Страница 32: ...to be displayed Pressing the or button will toggle between the two alarm setpoint prompts SP1 and SP2 If an incorrect security code is entered or a button is not pressed within ten seconds the transm...

Страница 33: ...tmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not li...

Страница 34: ...o the ATEX parameters and the systems shown in section 5 of this manual may therefore also be used for FM and cFM installations The BA474D Indicating Temperature Transmitter also has FM and cFM Associ...

Страница 35: ...33...

Страница 36: ...34...

Страница 37: ...35...

Страница 38: ...36...

Страница 39: ...37...

Страница 40: ...38...

Страница 41: ...39...

Страница 42: ...kely to occur in normal operation Zone 2 explosive gas air mixture not likely to occur and if it does will only exist for a short time Be used with gases in groups Group A propane Group B ethylene Gro...

Страница 43: ...ystem the BA474D may be installed in Zone 20 explosive atmosphere in the form of a cloud of combustible dust in air is continuously present or for long periods or frequently Zone 21 explosive atmosphe...

Отзывы: