6.4.7 Restart
This function determines what happens at the
end of each batch. There are three options:
Normal:
The display screen shows the
volume that has been
dispensed. Before another
batch can be started the
Reset
push-button must be operated.
The screen will then display
‘Ready’.
Quick:
The display screen shows the
volume that has been
dispensed. Operating the
Start
pushbutton will reset the
batch controller and start
another batch.
Auto restart: The display screen shows the
volume that has been
dispensed. After a configurable
restart delay (See 6.5.19) the
batch controller automatically
resets and starts another batch.
The number of batch cycles to
be performed is defined by the
Batch Cycle function, which is
contained in the Batch Setting
menu. See 6.5.18
Normal
Quick
Auto
Set Batch Restart
Highlight the required option and press
E
to
enter the selection.
6.4.8 Output 2
Output 2 is an isolated single pole solid state
switch contact that is connected to terminals
A3 and A4. It may be configured to output any
one of six different signals, or may be unused.
Unused
Control 2
Control 3
Flow alarm
Reset status
Batch status
Pulse Output
Set O/P 2 Function
Highlight the required option and press
E
to
enter the selection.
Note:
Two or more of the outputs may be
configured to output the same function.
6.4.9 Output 3
As Output 2 except terminals are A5 and A6.
6.4.10 Optional outputs 4, 5 and 6
Only available when factory fitted option is
installed in the BA454D batch controller.
Configuration is the same as for Output 2,
except terminal numbers are:
Output
Terminal numbers
4
A7 & A8
5
A9 & A10
6
A11 & A12
6.4.11 Pulse Output
Any of the batch controller outputs may be
configured as a pulse output. The number of
output pulses is proportional to the total
volume dispensed by the batch controller.
This Pulse Output function enables the pulse
output frequency to be reduced by one of five
dividing factors between 10 and 100,000.
Display / 1
Display / 10
Display / 100
Display / 1000
Display / 10000
Display / 100000
Set Output Rate
Highlight the required option and press
E
to
enter the selection.
Note:
Maximum output frequency is 4 Hz.
6.4.12 Clear Grand Total
The Grand Total is a record of the total
quantity of product dispensed since the Grand
Total was last reset to zero. It must be zeroed
every time the batch controller scaling is
changed
The Grand Total can be viewed in the
Information section of the System Menu – see
section 6.2 and Appendix 2.
CAUTION
After zeroing the old grand total
can not be recovered
To prevent the Grand Total being accidentally
zeroed, the clear instruction has to be
confirmed before it will be executed.
Clear G Total
Cancel
Clear Grand Total
20
Содержание BA454D
Страница 1: ...Issue 12 29th August 2014 BA454D Intrinsically safe Field mounting Batch Controller Issue 12 ...
Страница 14: ...Fig 10 Dimensions and terminal connections 14 ...
Страница 17: ...17 BLANK PAGE ...
Страница 18: ...18 Fig 11 System Settings Fig 11 System Settings ...
Страница 23: ...23 BLANK PAGE ...
Страница 24: ...24 Fig 14 Batch Settings ...
Страница 29: ...29 BLANK PAGE ...
Страница 30: ...30 Fig 16 Rate Settings ...
Страница 38: ...38 ...
Страница 39: ...39 ...
Страница 40: ...Appendix 2 Information menu 40 ...
Страница 43: ...43 ...
Страница 44: ...44 ...
Страница 45: ...45 ...
Страница 46: ...46 ...
Страница 47: ...47 ...
Страница 48: ...48 ...
Страница 49: ...49 ...