5. INSTALLATION
5.1 Location
The BA454D batch controller is housed in a
robust IP66 glass reinforced polyester (GRP)
enclosure incorporating an armoured glass
window and stainless steel fitting. It is suitable
for exterior mounting in most industrial
environments, including off-shore and waste
water treatment installations. Please consult
BEKA associates if high vibration is
anticipated.
The BA454D enclosure is surface mounting.
Accessory kits described in sections 9.2 of this
manual enable the instrument to be mounted
onto a vertical or horizontal pipe.
The field terminals and the two mounting holes
are located in a separate compartment with a
sealed cover allowing the instrument to be
installed without exposing the display
assembly.
The BA454D earth terminal is connected to the
internal EMC filters. For maximum radio
frequency interference rejection this terminal
should be connected to a local earth, or to a
cable screen which is earthed in the safe area.
The BA454D enclosure is supplied with a
bonding plate to ensure electrical continuity
between the three conduit / cable entries.
5.2 Installation Procedure
Fig 9 illustrates the instrument installation
procedure.
a.
Remove the instrument terminal cover by
unscrewing the two captive 'A' screws.
b.
Mount the instrument on a flat surface
and secure with two M6 screws through
the 'B' holes. Alternatively use one of the
mounting kits described in section 9.2
c.
Remove the temporary hole plug and
install an appropriate IP rated cable
gland or conduit entry. If more than one
entry is required, one or both of the IP66
stopping plugs may be replaced with an
appropriated IP rated cable gland or
conduit fitting.
d.
Connect the field wiring to the terminals
as shown in Fig 10.
e.
Replace the instrument terminal cover
and evenly tighten the two 'A' screws.
Fig 9 BA454D installation procedure
5.3 EMC
The BA454D complies with the requirements of
the European EMC Directive 2004/108/EC.
For specified immunity all wiring should be in
screened twisted pairs and the BA454D earth
terminal should be locally earthed or
connected to a cable screen which is earthed
in the safe area.
To prevent circulating currents, cable screens
should only be earthed at one point in the safe
area.
13
Содержание BA454D
Страница 1: ...Issue 12 29th August 2014 BA454D Intrinsically safe Field mounting Batch Controller Issue 12 ...
Страница 14: ...Fig 10 Dimensions and terminal connections 14 ...
Страница 17: ...17 BLANK PAGE ...
Страница 18: ...18 Fig 11 System Settings Fig 11 System Settings ...
Страница 23: ...23 BLANK PAGE ...
Страница 24: ...24 Fig 14 Batch Settings ...
Страница 29: ...29 BLANK PAGE ...
Страница 30: ...30 Fig 16 Rate Settings ...
Страница 38: ...38 ...
Страница 39: ...39 ...
Страница 40: ...Appendix 2 Information menu 40 ...
Страница 43: ...43 ...
Страница 44: ...44 ...
Страница 45: ...45 ...
Страница 46: ...46 ...
Страница 47: ...47 ...
Страница 48: ...48 ...
Страница 49: ...49 ...