background image

APPENDIX 1   
ATEX dust

 

certification

A1.0  ATEX dust certification

In addition to ATEX certification permitting
installation in explosive gas atmospheres which is
described in the main section of this instruction
manual, the BA414DF-F is available with optional
ATEX Ex ia IIIC and Ex ic IIIC dust certification. If
ATEX dust certification is required it must be
requested when the BA414DF-F Fieldbus Indicator
is purchased. 

CAUTION

Before installing a BA414DF-F Fieldbus
Indicator

in

the

presence

of

a

combustible

dust,

ensure

that

the

certification information label, which is
located on the top of the instrument,
specifies dust certification - see section
A1.3

A1.1

  

Ex ia IIIC  entity systems

The BA414DF-F Fieldbus Indicator has Ex ia IIIC
T100ºC Da IP66 certification. Installations should
comply with EN 60079-14

Electrical installation

design, selection and erection.

The Fieldbus Indicator may be installed in:

Zone 20 explosive atmosphere in the 

form of a cloud of 
combustible dust in air is 
continuously present, or for
long periods or frequently.

Zone 21 explosive atmosphere in the 

form of a cloud of 
combustible dust in air is 
likely to occur occasionally
in normal operation.

Zone 22 explosive atmosphere in the 

form of a cloud of 
combustible dust in air is not 
likely to occur in normal
operation, but if it does 
occur, will only persist for a 
short period.

Be used with dusts having a Minimum Ignition 
Temperature of:

Dust cloud

150

o

C

Dust layer on BA414DF-F  175

o

C

up to 5mm thick

Dust layer on BA414DF-F  Refer to
over 5mm thick.

EN 60079:14

At an ambient temperature between -20 and +60

o

C

The Indicator may be connected to any intrinsically
safe segment providing:

The device powering the fieldbus segment is
ATEX Ex ia IIIC certified for Zone 20, 21 or
22 applications, or Ex ib IIIC certified for
application in Zone 21 or 22. The output
parameters should be equal to or less than:

Uo

=

22V dc

Io

=

250mA dc

Po

=

1.2W

The segment can provide an additional 13mA
to power the Fieldbus Indicator.

The equivalent capacitance Ci of the
BA414DF-F Fieldbus Indicator is zero and
the equivalent inductance is insignificant.
Therefore these BA414DF-F parameters do
not need to be considered.

A1.2

  

Ex ic IIIC entity systems

The BA414DF-F Fieldbus Indicator also has
Ex ic IIIC certification for applications in Zone 22.
The higher Ui voltage allows the indicator to be
used with Power-i and intrinsically safe segment
couplers powered from Ex e fieldbus trunks.

The Fieldbus Indicator may be installed in:

Zone 22 explosive atmosphere in the 

form of a cloud of 
combustible dust in air is not 
likely to occur in normal
operation, but if it does 
occur, will only persist for a 
short period.

Be used with dusts having a Minimum Ignition 
Temperature of:

Dust cloud

150

o

C

Dust layer on BA414DF-F  175

o

C

up to 5mm thick

Dust layer on BA414DF-F  Refer to
over 5mm thick.

EN 60079:14

At an ambient temperature between -20 and +60

o

C

The BA414DF-F Fieldbus Indicator may be
connected to any intrinsically safe segment
providing:

The device powering the fieldbus segment is
ATEX Ex ia IIIC, ib IIIC or ic IIIC certified and
has output parameters equal to or less than:

Uo

=

32V dc

Io

=

125mA dc

Po

=

1W

9

Содержание BA414DF-F

Страница 1: ...Issue 9 27th March 2019 BA414DF F FOUNDATION fieldbus Intrinsically safe Field mounting Fieldbus Indicator Issue 9 ...

Страница 2: ...e 4 3 EMC 5 Maintenance 5 1 Fault finding during commissioning 5 2 Fault finding after commissioning 5 3 Servicing 5 4 Routine maintenance 5 5 Guarantee 5 6 Customer comments 6 Accessories 6 1 Scale and Tag marking 6 2 Tag plate 6 3 Pipe mounting kits 6 4 Fieldbus Interface Guide Appendix 1 ATEX dust certification Appendix 2 FM Approval for use in the USA and cFM Approval for use in Canada Appendi...

Страница 3: ... can be downloaded from the BEKA website www beka co uk System design information for non ATEX and dust approvals is shown in appendices to this manual 2 INTRINSIC SAFETY CERTIFICATION 2 1 ATEX certificate The BA414DF F has been issued with an EC Type Examination Certificate ITS06ATEX25313X by Notified Body Intertek Testing and Certification Ltd ITS confirming compliance with harmonised European s...

Страница 4: ...ut parameters as shown below FISCO Ex ia entity Ex ic entity Ui 17 5V 22 0V 32V Ii 380mA 250mA 125mA Pi 5 32W 1 2W 1W The maximum equivalent capacitance and inductance at terminals 1 2 is Ci 0nF Li 8µH 2 5 Certification Label Information The certification information label is fitted in a recess on the top outer surface of the enclosure It shows details of the ATEX certification a statement that th...

Страница 5: ...alent inductance is insignificant Therefore these BA414DF F parameters do not need to be considered 3 3 Ex ic entity systems The BA414DF F Fieldbus Indicator also has Ex ic certification with entity parameters for applications in Zone 2 The higher Ui voltage allows the indicator to be used with segment couplers powered by Ex e or Power i fieldbus trunks When installed in Zone 2 the BA414DF F Field...

Страница 6: ...ieldbus Indicator is 20 to 70o C 4 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure with two M6 screws through the B holes Alternatively use one of the mounting kits described in section 6 3 c Remove the temporary hole plug and install a ...

Страница 7: ...es Status of fieldbus variable has a quality of BAD or a fault state is active Display has not yet received data Variable source Fieldbus configuration Bargraph scale flashes Variable is outside the limits defined for the bargraph Bargraph configuration All display segments activated Display is initialising This is normal operation after a few seconds the firmware version will be displayed prior t...

Страница 8: ...display escutcheon remove the terminal cover by unscrewing the two A screws which will reveal two concealed D screws Unscrew all four D screws and carefully lift off the front of the instrument The location of all these screws is shown in Fig 2 After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling ...

Страница 9: ...ick Dust layer on BA414DF F Refer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is ATEX Ex ia IIIC certified for Zone 20 21 or 22 applications or Ex ib IIIC certified for application in Zone 21 or 22 The output parameters should be equal to or less than...

Страница 10: ...FISCO Field Device plus BEKA associates name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to show which of the certifications is being used The instrument serial number and date of manufacture are recorded on a separate label inside the terminal compartme...

Страница 11: ... 1 or 2 Class I Group A B Group C Group D Class II Group E F G Class III Zone 0 1 or 2 Class 1 Group IIC Group IIB Group IIA The FM and CFM entity parameters are identical to the ATEX parameters and like the ATEX certification confirm that the BA414DF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefo...

Страница 12: ...12 ...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...16 ...

Страница 17: ...17 ...

Страница 18: ...18 ...

Страница 19: ...llation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations but the local code of practice should also be consulted CAUTION installation in Zone 0 When installed in a Zone 0 potentially explosive atmosphere requiring EPL Ga apparatus the instrument shall be insta...

Отзывы: