For each segment an input pulse frequency in Hz
PuL5E fr
and a corresponding flowmeter K-factor
L-FACtor
are required. See section 7.1
Lineariser factory defaults are shown below:
Break point
PuL5EfrE L-FACtor
0.1
0Hz
1.00
1.1
5000Hz
1.00
Display
Summary of function
Add
Add a segment
Adds a new segment before the
displayed segment. The calibration of
existing segments is not changed, but
the
identification
number
of
all
subsequent segments is increased by
one.
See section 7.3
dEL
Remove a segment
Removes the displayed segment, the
identification
number
of
all
subsequent segments is decreased
by one.
See section 7.4
PuL5E Fr
Pulse input frequency
Defines the input frequency in Hz at
which
the
selected
lineariser
segments starts.
See section 7.5
L-FACtor
Flowmeter K-factor
The rate totaliser pulse input is
divided by
L-Factor
, which is usually
set to the K-factor of the flowmeter,
thus converting the flowmeter output
into engineering units.
L-Factor
may
be adjusted between
0 . 0001
and
99999.
Up to 16 values for
L-Factor
may be
entered, each starting at a specified
input pulse frequency
pul5e Fr..
See section 7.6
7.3 Add a segment:
Add
Add
is a sub-menu in the
FACtor
function that
enables a straight-line segment to be added to the
lineariser at any point.
Select
FACtor
in the
configuration menu and press
(
, which will reveal
one of four sub-functions.
If
Add
is not displayed
repeatedly press the
&
or
*
button to select
Add
followed by
(
which will cause the current segment
and the total number of lineariser segments to be
displayed as shown below:
Each time the
(
push button is operated a
segment will be added to the lineariser.
If
configuring the lineariser for the first time, repeatedly
press
(
until the required total number of
segments is shown on the right hand side of the
display.
Any number between 1 and 16 may be
selected.
If adding an additional segment to an already
configured lineariser, the insertion position, which is
shown on the left hand side of the display, can be
selected using the
&
or
*
push button.
When
inserting an additional segment, the identification
numbers of all segments equal to and above the
insertion point are increased by one.
Press
)
to return to the
Add
prompt in the
FACtor
sub-menu.
7.4 Remove a segment:
dEl
dEL
is a sub-menu in the
FACtor
function that
enables any segment to be removed from the
lineariser configuration.
Select
FACtor
in the
configuration menu and press
(
, which will reveal
one of four sub-functions.
If
dEL
is not displayed
repeatedly press the
&
or
*
button to select
dEL
followed by
(
which will cause the current segment
with the total number of segments to be displayed as
shown below:
Each time the
(
push button is operated the
current segment will be deleted from the lineariser.
If configuring the lineariser for the first time,
31
Содержание BA337E
Страница 4: ...4 ...
Страница 22: ...22 ...
Страница 23: ...23 ...
Страница 30: ...30 ...
Страница 41: ...41 ...
Страница 50: ...50 ...
Страница 51: ...51 ...
Страница 52: ...52 ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 59: ...59 ...
Страница 60: ...60 ...
Страница 61: ...61 ...