Summary of Programmable Functions

Display

      Description of function

'root'

Square root extractor

Turns the square root extractor for
linearising

the

output

from

differential flowmeters 'On' or 'OFF'.
See section 6.2 

'dSPL'

Digital display

Turns the 4½ digit display 'On' or
'OFF'.
See section 6.3

'rESn'

Display resolution & dummy zero

Selects the resolution of the least
significant display digit. May be set
to 1, 2, 5 or 10 digits.   
See section 6.4

'dZErO' Dummy trailing zero

Activates a dummy zero after the
4½ digit display so that larger
number may be displayed.
See section 6.5

'd.P.'

Decimal point

Positions a dummy decimal point
between any of the digits or turns it
off.
See section 6.6

'bAr'

Bargraph display

Selects a column or single segment
display, and defines whether the
input current is displayed on the left
hand or on both 100 segment
bargraphs.   See section 6.7

'CAL'

Calibration of displays using
external current source.

Enables the zero and span of the
digital indicator to be adjusted
using an external current source
such as a calibrator. The analogue
bargraph is linked to the digital
display

and

is

automatically

calibrated at the same time.      
When performed with an accurate
traceable current source, this is the
preferred method of calibration.
See section 6.8

Display      Description of function

'SEt'

Calibration

of

display

using

internal references.

Enables the zero and span of the
digital indicator to be adjusted
without the need for an accurate
input current or disconnection from
the 4/20mA loop.

The analogue

bargraph is linked to the digital
display

and

is

automatically

calibrated at the same time.      
See section 6.9

'Cond'

Indicator conditioning

This function provides access to a
password

protected

sub-menu

enabling the internal references to
be calibrated, and the mains (line)
frequency rejection to be selected.  
See section 6.10

                   

 CAUTION

Do not attempt to change
the frequency of the mains
(line) filter frequency or
recalibrate

the

internal

references without reading
section 6.10 of this manual 

'FrE'

Frequency

rejection

Defines the mains (line) frequency
at

which

the

indicator

has

maximum ac rejection. 50 or 60Hz
may be selected.

This function

must be set before the instrument
is calibrated as it affects the
indicator display.
See section 6.10.1

'rEF'

Calibration of

internal   
           references

The

indicator

contains

two

references representing 4 and
20mA. These internal references
are used when the indicator display
is calibrated without an external
current calibrator, and when the
input

current

is

displayed

in

milliamps. See the SEt and C--P
functions.

If either of these

functions is to be used, the internal
references should be periodically
calibrated.
See section 6.10.2

Содержание ba326c

Страница 1: ...rinsically safe loop powered analogue bargraph and digital indicator Issue 12 For instrument with serial numbers above 071235 01 001 Alarm setpoints Digital display Certification label Alarm annunciat...

Страница 2: ...ver and under range 7 Calibration Examples 7 1 Using an external current source 7 2 Using the internal references 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissio...

Страница 3: ...ATEX Directive 2014 34 EU The EC Type Examination Certificate specifies that under fault conditions the output voltage current and power at input terminals 1 and 3 will not exceed those specified for...

Страница 4: ...y be installed in any of the European Economic Area EEA member countries ATEX certificates are also accepted for installations in Switzerland This manual describes installations which conform with EN6...

Страница 5: ...e incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded 3 4 Certification label information The...

Страница 6: ...ated then two Zener barriers a two channel Zener barrier or a galvanic isolator must be used When the hazard is a IIC gas and two single channel Zener barriers or a two channel Zener barrier are used...

Страница 7: ...rast when viewed from directly ahead and slightly below the centre line of the instrument For reflective displays there is very little degradation of contrast when viewed from above the centre line bu...

Страница 8: ...AL and ALr2 Access to the programme menu is obtained by operating the P and E push buttons simultaneously If the instrument is not protected by a security code the first parameter root will be display...

Страница 9: ...ration See section 6 8 Display Description of function SEt Calibration of display using internal references Enables the zero and span of the digital indicator to be adjusted without the need for an ac...

Страница 10: ...On or OFF If set as required press E to return to the menu or press the Up or Down button to change the setting followed by the E button to return to the main menu 6 4 Display resolution rESn This fun...

Страница 11: ...11...

Страница 12: ...The indicator will display ZErO which is a request for a 4mA input current Adjust the external current calibrator to 4 000mA and again press P which will reveal the current zero display Each digit ex...

Страница 13: ...a password protected sub menu which allows the mains line frequency at which the indicator has maximum ac rejection to be selected and the two internal references to be calibrated To gain access to t...

Страница 14: ...internal references which should be periodically calibrated see section 6 10 2 6 12 Null display function null This function enables the BA326C analogue bargraph to operate as a deviation indicator di...

Страница 15: ...able functions can be obtained by moving the internal security link to the override position The original security code can then be viewed by selecting CodE from the main menu and pressing P To gain a...

Страница 16: ...or off by the Up or Down buttons Select OFF and press E to return to the main menu Step 4 Select frequency of max rejection Scroll though the main menu until Cond is displayed and press P The indicat...

Страница 17: ...ter the code and the first parameter root in the main menu will be displayed Step 2 Square root extractor With root displayed press P which will reveal the root extractor status The root extractor can...

Страница 18: ...ly display input has a voltage large ripple content Unable to Incorrect Enter correct enter the security security code or fit programme code security link in mode entered override position See Fig 9 8...

Страница 19: ...nstrument terminal block s by gently pulling and remove the rear panel which is secured by six screws see Fig 9 The electronic assembly may then be pulled out of the enclosure to reveal the display la...

Страница 20: ...menu provides direct access to both setpoints from the display mode without giving the operator access to the programme and alarm menus A different security code may be included to prevent tampering o...

Страница 21: ...ctance specified by the system certificate of the circuit connected to each alarm Fig 13 Typical alarm application 9 2 3 Programming and adjustment When an alarm card is added to a BA326C the main pro...

Страница 22: ...section 9 2 12 9 2 4 Alarm enable EnbL This function allows the alarm to be enabled or disabled without altering any of the alarm parameters To check or change the function select EnbL from the alarm...

Страница 23: ...using the Up and Down push buttons and the P button to move to the next digit When the required hysteresis has been entered press E to return to the alarm menu Fig 14 Alarm Programme Menu P P E ALr2 E...

Страница 24: ...1 Display alarm identification FLASH The status of each alarm is always shown by an alarm annunciator located above the digital display In addition to this annunciator this function provides an alarm...

Страница 25: ...t may be adjusted using the Up and Down push buttons and the P button to move to the next digit When the required setpoint has been entered pressing E will return the display to the SP1 or SP2 prompt...

Страница 26: ...ect CAL from the main menu and press P to enter the Add function press P again to reveal the current and total number of break points Each subsequent operation of the P push button will introduce an a...

Страница 27: ...the Add function described above When the required number of break points has been entered return to the sub menu by pressing E The indicator will display Add or dEL depending upon the last function u...