background image

9.3.6  Setpoint adjustment:  

5P1.

x & 

5P2.

x

The  speed  alarm  setpoints  

5P1.5peed

 and  

5P2.5peed

may  be  positioned  anywhere  between  

0000000

 and

9999999

,  and  the  run-time  alarm  setpoint  

5P1.Hour5

and  

5P2.Hour5

 anywhere  between  

0000.0

 and  

9999.9

hours.

All  the  setpoints  are  adjusted  in  the  same  way, for
example, to adjust the setpoint of Alarm 1 which has
been  configured  to  operate  on  the  speed  display.
Using the  

&

 or  

*

 push button select  

5P1.5peed

 in

the 

AL1

 sub-menu and press 

which will reveal the

existing setpoint with one digit flashing.  The required
setpoint   can   be   entered   using   the  

&

 or  

*

 push

button to adjust the flashing digit and the 

button to

transfer  control  to  the  next  digit.      When  set  as
required press 

to enter the value and return to the

5P1.5peed

 prompt in the alarm 1 sub-menu.

9.3.7  Alarm function:  

Hi

 

.

 

Lo

Alarm  1  and  Alarm  2  are  totally  independent,  both
may be Hi or Lo, or one may be conditioned as a Hi
alarm and the other as a Lo alarm.

Using the 

&

 or 

push button select 

Hi

 

.

 

Lo

 from the

selected alarm sub-menu and press  

(  

to check or

change the function.  The  

&

 or  

*

 push button will

toggle the alarm function between  

Hi

 and  

Lo

, when

set as required, press the  

)  

button to return to the

Hi

 

.

 

Lo’ prompt in the alarm sub-menu.

9.3.8  Alarm output status:  

no

 

.

 

nC

Each single pole alarm output may be open or closed
in  the  non-alarm  condition.    When  the  BA314NG
power supply is turned off or disconnected, the alarm
output(s)  will  open  irrespective  of  whether  normally
open or normally closed outputs have been selected.
Therefore, when designing an alarm system normally
closed 

nc

 should be selected so that the output opens

when an alarm occurs or if the power supply fails.

Using the 

&

 or 

*

 push button select 

no

 

.

 

nC

 from the

selected alarm sub-menu and press  

(  

to check or

change the function. The  

&

 or  

*

 push button will

toggle the contact status between 

no

 and 

nC

, when set

as required, press the 

button to return to the 

no

 

.

 

nC

prompt in the alarm sub-menu.

9.3.9  Hysteresis:  

H5tr

Hysteresis is only available on speed alarms so the

H5tr

 function only appears in the configuration sub-

menu  when  alarm  

tYPE

  has  been  set  to  

5PEEd

.

During configuration hysteresis is shown in the units
of  

5PEED

 previously configured for  the Tachometer

display.

Using the  

&

 or  

*

 push button select  

H5tr

 in the

selected alarm sub-menu and press  

(

 which will

reveal the existing hysteresis with one digit flashing.
The  required  hysteresis  can  be  entered  using  the

&

 or 

*

 push button to adjust the flashing digit and

the  

(  

button to transfer control to the next digit.

When set as required press  

)

 to enter the value

and  return  to  the  

H5tr

  prompt  in  the  alarm  sub-

menu.

e.g.  A Tachometer configured to display a rotational
speed of 0 to 500 RPM, with a high alarm set at
400 RPM and hysteresis of 10 RPM will perform as
follows:

The high alarm will be activated when speed
equals or exceeds 400 RPM, but will not reset
until the speed falls below 390 RPM.

9.3.10  Alarm delay:  

dELA

This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition  occurring.    The  delay  can  be  set  in  1
second increments up to 3600 seconds.  If a delay is
not required zero should be entered.

To adjust the delay select  

dELA

 using the  

&

 or 

*

push  button  in  the  selected  alarm  sub-menu  and
press 

which will reveal the existing delay time in

seconds with one digit flashing.  The required delay
time can be entered using the 

&

 or 

*

 push button

to  adjust  the  flashing  digit  and  the  

(  

button  to

transfer  control  to  the  next  digit.      When  set  as
required press  

)  

to enter the value and return to

the 

dELA

 prompt in the alarm sub-menu.   The alarm

annunciator will start flashing immediately an alarm
condition occurs and will continue for the delay time,
after which the alarm output will be activated and the
alarm annunciator will be permanently activated.

34

Содержание BA314NG

Страница 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Страница 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Страница 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Страница 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Страница 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Страница 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Страница 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Страница 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Страница 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Страница 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Страница 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Страница 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Страница 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Страница 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Страница 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Страница 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Страница 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Страница 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Страница 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Страница 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Страница 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Страница 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Страница 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Страница 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Страница 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Страница 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Страница 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Страница 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Страница 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Страница 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Страница 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Страница 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Страница 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Страница 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Страница 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Страница 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Страница 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Отзывы: