background image

6.0  CONFIGURATION & CALIBRATION

The  BA314NG  Tachometer  is  configured  and
calibrated via four front panel push buttons.   All the
configuration  functions  are  contained  in  an  easy  to
use intuitive menu that is shown diagrammatically in
Fig 10.

Each menu function is summarised in section 6.3 of
this manual and each summary includes a reference
to more detailed information.

When factory fitted optional alarms, pulse and 4/20mA
outputs  are  included,  additional  functions  appear  in
the   configuration   menu,   which   are   described
separately in section 9.

All  new  Tachometer  are  supplied  calibrated  as
requested at the time of ordering.  If calibration is not
requested,  the  Tachometer  will  have  factory  default
configuration as shown in the following table, but can
easily be re-configured  on-site.

 Function

Display             Default

Input

inP

 

.

 

tYPE

oP

 

.

 

CoL

Debounce

dEbounCE

dEFAuLt

Update

uPdAtE

0

 

.

 

5

Run-time display

di5P-2

on

Decimal point (speed)

dP

0000

 

.

 

0

Speed scale factor

5CALE

 

.

 

5

001

 

.

 

00

Timebase

t-bA5E

tb-60

Filter

FiLter

24

Clip-off

CLP-oFF

0000

 

.

 

0

Local run-time reset

clr tot

oFF

Local grand total
   run-time reset.

Clr gtot

oFF

Security code

CodE

0000

6.1  Configuration structure

Fig 9 shows the BA314NG calibration structure.  

The pulse input is divided by  

5CALE.5

 to provide the

required  Tachometer  speed  display  in  engineering
units.    e.g.  if  a  sensor  monitoring  a  rotating  shaft
generates  18  pulses  per  revolution,  to  produce  a
display in revolutions 

5CALE.5

 should be set to 18.0.

The  timebase  

t-bA5E

  is  a  multiplying  factor  that

determines  whether  the  Tachometer  displays  speed
per second, per minute or per hour.  

The Tachometer incorporates a run-time counter that
displays  the  time  in  hours  that  the  speed  of  the
monitored  machinery  has  been  equal  to  or  greater
than the clip-off value.

Fig 9  Calibration structure

6.2  Accessing configuration functions

Throughout this manual push buttons are shown as

&

,  

*

,  

(

 and  

).

   Legends  displayed  by  the

instruments are shown in a seven segment font as
they  appear  on  the  Tachometers  e.g.  

inPut

 and

uPdAtE

.

Access  to  the  configuration  menu  is  obtained  by
operating  the  

(

 and  

)

 push  buttons

simultaneously.   If the instrument is not protected by
a  security  code  the  first  parameter  

inPut

 will  be

displayed.  If a security code other than the default
code 

0000

 has already been entered, the instrument

will display 

CodE

.  Press 

(

 to clear this prompt and

enter the security code for the instrument using the

&

 or  

*

 push button to adjust the flashing digit,

and  the  

(  

push  button  to  transfer  control  to  the

next digit.   If the  correct code  has been  entered
pressing  

)  

will cause the first parameter  

inPut

 to

be displayed.  If an incorrect code is entered, or a
push button is not operated within ten seconds, the
instrument  will  automatically  return  to  the  display
mode.

All configuration functions and prompts are shown
on the upper eight digit display.

Once  within  the  configuration  menu  the  required
parameter can be selected by scrolling through the
menu  using  the  

&

 or  

*

 push  buttons.  The

configuration  menu  is  shown  diagrammatically  in
Fig 10.

When  returning  to  the  display  mode  following
reconfiguration,  the  Tachometer  will  display  

dAtA

followed by 

5AVE

 while the new information is stored

in permanent memory.

13

Содержание BA314NG

Страница 1: ...Issue 5 9th July 2019 BA314NG Ex nA and Ex tc Tachometer Issue 5...

Страница 2: ...dAtE 6 8 Run time display di5P 2 6 9 Position of the decimal points dP 6 10 Speed scale factor 5CALE 5 6 11 Timebase t bA5E 6 12 Display filter FiLtEr 6 13 Clip off CLP oFF 6 14 Local reset LoC clr 6...

Страница 3: ...larm silence time 5IL 9 3 12 Flash display when alarm occurs FL5H 9 3 13 Access Setpoint AC5P 9 3 14 Adjusting alarm setpoints from the display mode 9 4 4 20mA output 9 4 1 Ex nA certification 9 4 2 S...

Страница 4: ...m compliance with the European ATEX Directive 2014 34 EU For international applications the BA314NG also has IECEx certification which is described in Appendix 2 For applications in the USA and Canada...

Страница 5: ...the Tachometer may be configured to provide direct access to the alarm setpoints from the display mode when the and buttons are operated simultaneously See 9 3 13 and 9 3 14 2 3 Displays The BA314NG...

Страница 6: ...the Type Examination Certificate This allows the Tachometer to be adjusted and configured live when installed in Zones 2 When connected to a suitable system the BA314NG Tachometer may be installed in...

Страница 7: ...ety parameters Input Output Type of input Link 3 4 Ui Uo Io Switch contact Yes 15V 10 5V 9 2mA Proximity detector Yes 15V 10 5V 9 2mA Open collector Yes 15V 10 5V 9 2mA Magnetic pick off No 30V 1 1V 0...

Страница 8: ...that terminals 2 6 and RS2 are interconnected within the BA314NG See Fig 1 4 1 Power supply The BA314NG Tachometer requires a minimum of 10V between terminal 1 2 and consumes 10mA without optional bac...

Страница 9: ...eshold and rise above the upper thresholds shown in the following table Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0...

Страница 10: ...d associated wiring should be able to withstand a 500V rms insulation test to earth The BA314NG contains a configurable debounce circuit to prevent false triggering See section 6 6 4 2 6 Voltage pulse...

Страница 11: ...the bottom right hand corner the back box for interconnecting cable screens The BA314NG Tachometer may be pipe mounted using a BA393G pipe mounting kit 5 2 Installation Procedure Fig 6 illustrates the...

Страница 12: ...instrument is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as a...

Страница 13: ...factor that determines whether the Tachometer displays speed per second per minute or per hour The Tachometer incorporates a run time counter that displays the time in hours that the speed of the mon...

Страница 14: ...on or oFF See section 6 8 Display Summary of function dP Decimal points Defines the position of the decimal point in the Tachometer speed display See section 6 9 5CALE 5 Speed scale factor 5CALE 5 is...

Страница 15: ...6 Display Summary of function CLr Gtot Resets grand total run time to zero This function resets the grand total run time to zero from within the configuration menu when CLr YE5 is selected and 5urE is...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...ges such as those resulting from a mechanical contact closing and bouncing Three levels of protection may be selected and the amount of debounce applied depends upon the type of Tachometer input that...

Страница 19: ...g shaft generates 18 pulses per revolution to produce a Tachometer speed display in revolutions 5CALE 5 should be set to 18 0 The units of the Tachometer speed display are pulses per unit of time The...

Страница 20: ...sed it is not necessary to enter a clip off value see 6 8 To check or change the clip off threshold select CLP oFF from the configuration menu and press which will reveal the current setting The thres...

Страница 21: ...isplayed and then press which will result in a 0000 prompt being displayed with the first digit flashing This is a request for the instruction to be confirmed by entering 5urE using the or button to a...

Страница 22: ...the wires entering the hazardous area should be individually fused and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fus...

Страница 23: ...ting on or oFF The function can be changed by pressing the or push button followed by the button to return to EnbL prompt in the sub menu 6 20 6 Source of output pulse 5ourCE The output pulse may be d...

Страница 24: ...to select the required value followed by the button to return to durAtion prompt in the sub menu Note This function only appears in the pulse output sub menu when 5CALEd is selected in the 5ource sub...

Страница 25: ...al between display updates Using the or button select uPdAtE in the configuration menu and press to reveal how frequently the Tachometer display is updated Using the or push button select 0 5 0 5 seco...

Страница 26: ...h buttons The button will transfer control to the second digit which controls the step response and should be set to 0 in the same way Finally enter the selection and return to the FiLtEr prompt in th...

Страница 27: ...s unauthorised access to the configuration menu Using the or button select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the sec...

Страница 28: ...ion change Re enable both alarms See 9 3 4 8 2 Fault finding after commissioning EN 60079 17 Electrical installations inspection and maintenance permits live maintenance in Zone 2 if a risk analysis d...

Страница 29: ...your local BEKA agent It is helpful if a brief description of the fault symptoms is provided 8 6 Customer comments BEKA associates is always pleased to receive comments from customers about our produ...

Страница 30: ...with factory fitted dual isolated solid state single pole alarm outputs that may be independently configured Each may be configured as a speed or run time alarm with a high or low function having a no...

Страница 31: ...the means of isolation is essential for their effective use It is also necessary to ensure that the maintenance procedure makes sure that unauthorised re closure of the switches does not occur It is n...

Страница 32: ...t and the alarm output being activated See section 9 3 10 5IL Alarm silence time Defines the time that the alarm output remains in the non alarm condition following acceptance of an alarm See section...

Страница 33: ...to return to the alarm sub menu 9 3 5 Type of alarm tYPE Alarm 1 and Alarm 2 are totally independent both may be speed or run time alarms or one may be conditioned for speed and the other for run time...

Страница 34: ...ggle the contact status between no and nC when set as required press the button to return to the no nC prompt in the alarm sub menu 9 3 9 Hysteresis H5tr Hysteresis is only available on speed alarms s...

Страница 35: ...l adjustment is provided by a separate security access code Using the or push button select AC5P from the configuration menu and press to reach the enable function EnbL Pressing will reveal the existi...

Страница 36: ...the or push button and the button to transfer control to the next digit When the required setpoint has been entered pressing will return the display to the 5P1x or 5P2x prompt from which the other se...

Страница 37: ...ed and contain a means of isolation These two requirements may be satisfied by installing DIN rail mounted terminals incorporating a fuse which can easily be opened as shown in Fig 2 to provide isolat...

Страница 38: ...g the or push button select 4 000 in the 4 20mA output sub menu and press to reveal the existing speed display with one digit flashing The required display can be entered using the or push button to a...

Страница 39: ...cate indicated by the certificate number s X suffix These state that the BA314NG Tachometer should be a Supplied from a limited energy circuit with output parameters in normal operation equal to or le...

Страница 40: ...ical to the ATEX safety parameters described in the main section and in Appendix 1 of this manual The IECEx certificate may be downloaded from the BEKA associates or the IECEx website or may be reques...

Страница 41: ...T5 Gc Zone 22 AEx ic tc IIIC T80 C Dc Ta 40 C to 60 C cETL codes for Canada Ex nA ic IIC T5 Gc Ex n IIC T5 Gc Ex ic tc IIIC T80 C Dc Class III Div 2 Class II Div 2 Gp F G Ta 40 C to 60 C The ETL and...

Отзывы: