Appendix 2
IECEx certification
A2.0 The IECEx Certification Scheme
IECEx is a global certification scheme for explosion
protected products which aims to harmonise
international certification standards. For additional
information about the IECEx certification scheme and
to view the BEKA associate certificates, please visit
www.iecex.com
A2.1 IECEx Certificate of Conformity
The BA307E-SS and the BA327E-SS loop powered
indicators and the optional accessories have been
issued with an IECEx Certificate of Conformity
number IECEx ITS 14.0048X which specifies the
following certification codes:
Ex ia IIC T5 Ga
Ex ia IIIC T80ºC Da IP20
Ta = -40ºC to 70ºC
The specified gas and dust intrinsic safety parameters
are identical to the ATEX safety parameters described
in this manual.
The IECEx certificate may be downloaded from
www.beka.co.uk, www.iecex.com or requested from
the BEKA sales office.
A2.2 Installation
The IECEx and ATEX certificates specify identical
safety parameters and installation requirements for
both approvals as defined by IEC / EN 60079-14. The
ATEX gas and dust installation requirements specified
in section 5 and Appendix 1 of this manual may
therefore be used for IECEx installations, but the local
code of practice should also be consulted.
A2.3
Special conditions for use in IIIC dusts
The IECEx intrinsic safety certificate has an ‘X’
suffix indicating that for some applications special
conditions apply for safe use which are identical to
ATEX special conditions for safe use.
a.
When installed in an Ex px, Ex py or Ex pz
panel enclosure the indicator must be powered
by an appropriately rated Zener barrier or
galvanic isolator located in a safe area.
The supply circuit for indicators used in the
equipment with pressurised type of protection
shall be rated for a prospective short circuit
current of not more than 10kA.
b.
When installed in an Ex e panel enclosure the
indicator must be powered by an appropriately
rated Zener barrier or galvanic isolator located
in a safe area.
c.
When installed in an Ex ta, Ex tb or Ex tc panel
enclosure the indicator must be powered by an
appropriately rated Zener barrier or galvanic
isolator located in a safe area.
d.
For use in Group IIIC conductive dust
atmospheres the indicator shall be mounted
such that the instrument terminals have at least
IP6X protection.
A2.4 IECEx certification label
The IECEx certification information is shown on a
label fitted in a recess on the top outer surface of
the instrument enclosure.
30
Содержание BA307E-SS
Страница 12: ...12 ...
Страница 17: ...17 ...
Страница 22: ...22 ...
Страница 32: ...32 ...
Страница 33: ...33 ...
Страница 34: ...34 ...
Страница 35: ...35 ...
Страница 36: ...36 ...
Страница 37: ...37 ...
Страница 38: ...38 ...
Страница 39: ...39 ...
Страница 40: ...40 ...
Страница 41: ...41 ...
Страница 42: ...42 ...