7.  MAINTENANCE

7.1 Fault finding during commissioning

If the BA304NC fails to function during
commissioning the following procedure should be
followed:

Symptom          Cause                   Solution

No display

Incorrect

There should be 1V

wiring

between terminals 1 &
3 with terminal 1
positive.

No display 

Incorrect 

Check that a current

with 0V  

wiring or

is flowing in the loop.

between no 

power

terminals 1

supply.

and 3.

Insufficient

Check supply voltage

loop voltage  and voltage drops
to operate 

caused by all

BA304NC.

components in the loop.

No display

Indicator 

Check that the three

with 4V

assembly 

screws securing the

between 

not correctly  indicator assembly are

terminals 1

installed in

tightened.

and 3

enclosure.

BA304NC 

Positive

The BA304NC has been

displays 1

over-range

incorrectly calibrated &
is trying to display a
number greater than
1999.

BA304NC

Negative 

The BA304NC has been

displays -1

over-range

incorrectly calibrated &
is trying to display a
number less than
-1999.

Unstable

4/20mA 

Check loop supply

display

input has a 

voltage.

large ripple

7.2  Fault finding after commissioning

CAUTION!

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live maintenance should only be
performed when there is no risk of a
flammable atmosphere being present,
and dust or water can not enter the
enclosure.  Before replacing enclosure
cover ensure that the sealing gasket is
undamaged and free from dirt and
foreign bodies.

If a BA304NC fails after it has been functioning
correctly, the following procedure should be
followed:

Symptom        Cause                 Solution

No display

No power 

Check that a current

with 0V

supply

is flowing in the loop.

between
terminals 1
and 3

No display

Indicator 

Check that the three

with 4V 

assembly 

screws securing the

between 

not correctly  indicator assembly are

terminals 1

installed in

tightened.

and 3

enclosure.

Unstable

4/20mA 

Check loop supply

display

input has a  voltage.
large ripple

If this procedure does not reveal the cause of the
fault, it is recommended that the indicator
assembly is removed from the enclosure and
replaced.  This can be done without disconnecting
power.  If the replacement assembly functions, the
fault is within the original indicator assembly.  If the
indicator is still faulty, it is likely that the fault is
within the enclosure assembly or field wiring.

Содержание BA304NC

Страница 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Страница 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Страница 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Страница 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Страница 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Страница 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Страница 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Страница 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Страница 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Страница 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Страница 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Страница 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Отзывы: