7.  LINEARISER

A sixteen segment, seventeen break-point (0 to 16)
lineariser may be selected in the ‘FunC’ section of
the  configuration  menu.    The  position  of  each
break-point is fully adjustable so that the slope of
the straight line between break-points can be set to
compensate  for  input  non-linearity,  thus  allowing
the  indicator  to  display  a  non-linear  process
variables in linear engineering units. Each break-
point  must  occur  at  a  current  greater  than  the
preceding break-point and less than the following
break-point,  in  the  range  3.8  to  21.0mA.    If this
requirement is not observed when configuring the
lineariser  the  indicator  will  display  'FaiL'  and  the
configuration adjustment which produced the error
message will be ignored.   Fig 7 shows a typical
linearised indicator characteristic.

Fig 7 shows a typical linearising characteristic

Selecting  ‘Lin’  in  the  ‘FunC’  section  of  the
configuration  menu  activates  the  lineariser,  this
does not change the configuration menu shown in
Fig  6,  but  the  'CAL'  and  'SEt'  functions  are
extended as shown in Fig 8.    As with a linear
indicator,  calibration  of  the  lieariser  may  be
performed  with  an  external  current  source  using
the  'CAL'  function,  or  with  the  internal  reference
using the 'SEt' function.

The lineariser calibration is retained irrespective of
how the indicator function ‘FunC’ is subsequently
changed.   It is therefore possible  to select and
deselect  the  lineariser  without  having  to
reconfigure it each time.

The  lineariser  calibration  may  be  reset  to  the
factory  default  settings  without  changing  the
indicator  configure  using  the  'LtAb'  function
described in section 6.11.

7.1  Lineariser calibration using an external 

current source.

This  method  allows  direct  calibration  of  the
lineariser with an external current source and is the
preferred method when traceability is required.   If
the  exact  system  non-linearity  is  unknown,  this
method  also  allows  direct  calibration  from  the
variable to be displayed.  e.g. the output from a
level sensor in an irregular tank may be displayed
in  linear  volumetric  units  by  filling  the  tank  with
known  incremental  volumes  and  calibrating  the
indicator to display the sum of the increments at
each break-point.

The number of break-point required should first be
entered using the 'Add' and 'dEL'  functions.  In
both  these  sub-functions  the  indicator  initially
displays  the  current  break-point  and  the  total
number  of  break-points  being  used  as  shown
below.

Display

      Description of function

'Add'

Add a break-point

Adds  a  new  break-point  before  the
displayed break-point.  The calibration
of existing break-points is not changed,
but  the  identification  number  of  all
subsequent  break-points  is  increased
by one.

'dEL'

Remove a break-point

Removes the displayed break-point and
joins  the  preceding  break-point to  the
following  break-point  with  a  straight
line.   The identification number of all
subsequent  break-points  is  decreased
by one.

To add a break-point use the 

 or 

 button to

select 'CAL' from the configuration menu and press

P

 

which will result in the

 

'Add' sub-function prompt

being displayed.  To enter the sub-function press 

P

which will reveal the current break-point and the
total  number  of  break-points  which  have  already
been entered.    When adding a break-point the
insertion position can be selected using the 

 and

 push  buttons  followed  by  

P

 push  button  to

insert  the  additional  break-point.    In  previously
uncalibrated  linearisers  each  new  break-point
should  be  added  in  front  of  the  highest  existing
break-point, if this sequence is not followed a 'FaiL'
message  will  occur  in  the  'Pt5'  function.    See
example in section 7.1.1.

Содержание BA304E

Страница 1: ...Issue 8 5th May 2016 BA304E BA324E intrinsically safe loop powered field mounting indicators Issue 8 ...

Страница 2: ...eariser error message 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 External keypad 9 2 Units of measurement and instrument identification 9 3 Alarms 9 3 1 Solid state output 9 3 2 Intrinsic safety 9 3 3 Configuration and adju...

Страница 3: ...Type Examination certificate specifies that under fault conditions the output voltage current and power at the 4 20mA input terminals will not exceed those specified for simple apparatus in Clause 5 7 of EN 60079 11 which simplifies installation and documentation For international applications both models have IECEx certification which is described in Appendix 2 For installations in the USA and Ca...

Страница 4: ...ation ATEX dust and IECEx approvals are described in Appendixes 1and 2 3 1 ATEX gas certification Notified Body Intertek Testing and Certification Ltd have issued both models with a common EC Type Examination Certificate number ITS11ATEX27253X This confirms compliance with harmonised European standards and it has been used to confirm compliance with the European ATEX Directive for Group II Categor...

Страница 5: ... ATEX certification information and BEKA associates name and location Non European certification information may also be shown The instrument serial number and date of manufacturer are recorded on a separate label inside the terminal compartment BA304E certification label BA324E certification label 4 SYSTEM DESIGN FOR GAS HAZARDOUS AREAS 4 1 Transmitter loops Both models may be connected in series...

Страница 6: ...he indicator plus the interface When a high integrity earth connection is already available a Zener barrier is usually the least expensive option If an earth connection is not available or isolation is required a galvanic isolator is the correct choice If one side of the 4 20mA current loop may be earthed a single channel Zener barrier provides the lowest cost protection If the 4 20mA signal is no...

Страница 7: ...thed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosures are fitted with a bonding plate to ensure electrical continuity between the three conduit cable entries 5 2 Installation Procedure Fig 4 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the in...

Страница 8: ...ation Default Configuration BA304E BA324E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display mode C P Tare tArE Off Off 6 1 Summary of configuration functions This section summarises each of the main configuration functions an...

Страница 9: ...9 ...

Страница 10: ...Lin 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to change the setting followed by the E button to return to the configuration menu Std Linear Provides a linear relationship between the 4 20mA indicator input current and the indic...

Страница 11: ...between the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasing input current will cause the display to decrease 6 6 Calibration using internal reference SEt Using the SEt function the indicator can be calibrate...

Страница 12: ...setting between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments are configured with the default security code 0000 which allows unrestricted access to all configuration functions To ent...

Страница 13: ...direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct calibration from the variable to be displayed e g the output from a level sensor in an irregular tank may be displayed in linear volumetric units by filling the tank with known incremental volumes ...

Страница 14: ...14 ...

Страница 15: ...ollowing break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function described in section 6 11 each additional break point should be added before the highest existing breakpoint The first additional break point should be added before the default break point 1 1 wh...

Страница 16: ...nction by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal the starting point for the first break point 0 n where n is the total number of break points entered Press P and use the and buttons and the P button to move between digits to ...

Страница 17: ... indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be open circuit 8 3 Servicing All BA304E and BA324E loop powered indicators are interchangeable if...

Страница 18: ...on Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 9 3 Alarms CAUTION These alarms outputs should not be used for criti...

Страница 19: ...ied by clause 5 7 of EN 60079 11 for simple apparatus This simplifies system documentation and allows the alarm output terminals 8 9 and 10 11 to be connected to almost any intrinsically safe circuit protected by a Zener barrier or galvanic isolator providing the output parameters of the circuit do not exceed Uo 30V dc Io 200mA Po 0 84W The maximum equivalent capacitance and inductance between eac...

Страница 20: ...20 ...

Страница 21: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or normally closed output Sets the alarm output open or closed in the non alarm condition See section 9 3 7 HStr Hysteresis Adjusts the alarm hysteresis See section 9 3 8 dELA Alarm delay time Introduce...

Страница 22: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press P to reveal the setting The function may be changed by pressing the or button followed by the E button to return to the alarm configuration menu 9 3 8 Hysteresis HStr Hysteresis is shown in the units...

Страница 23: ...aving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct setpoint access menu is enabled and the separate security code entered from the ACSP function in the alarm configuration menu as shown in Fig 12 To change the menu parameters select ACSP from the con...

Страница 24: ...oint plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargraph The bargraph area below the low alarm setpoint and the area above the high alarm setpoint are activated The displayed variable is represented by an activated bar which moves between these low and ...

Страница 25: ...those specified by clause 5 7 of EN 60079 11 for simple apparatus which simplifies system design and documentation Providing the increased voltage drop can be tolerated the intrinsic safety and system design described in sections 3 and 4 of this manual remain valid with the backlight loop powered 9 4 2 Separately powering the backlight The optional backlight may also be powered from a separate saf...

Страница 26: ...al pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket secured by a single V bolt Will clamp to any vertical or horizontal pipe with an outside diameter between 40 and 80mm ...

Страница 27: ... in normal operation but if it does occur will only persist for a short period Be used with dust in subdivisions IIIA combustible flyings IIIB non conductive dust IIIC conductive dust Having a Minimum Ignition Temperature of Dust cloud 120 C Dust layer on indicator 155 C up to 5mm thick Dust layer on indicator Refer to over 5mm thick EN 61241 14 At an ambient temperature between 40 and 70 C A1 2 C...

Страница 28: ... apply when the indicator is installed in Zone 1 or in Zone 2 The specified IECEx gas and dust intrinsic safety parameters are identical to the ATEX safety parameters described in the main section and Appendix 1 of this manual The IECEx certificate may be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A2 2 Installation The IECEx and ATEX certificates specify i...

Страница 29: ...rinsically Safe Systems for Hazardous Classified Locations and with the National Electrical Code ANSI NFPA70 Installations in Canada must comply with the Canadian Electrical Code C22 2 The BA304E and BA324E have T5 rating at ambient temperatures up to 70ºC and may be used with the following gases and dusts Intrinsic Safety Division 1 or 2 Class I Group A B Group C Group D Class II Group E F G Clas...

Страница 30: ...30 ...

Страница 31: ...31 ...

Страница 32: ...32 ...

Страница 33: ...33 ...

Страница 34: ...34 ...

Страница 35: ...35 ...

Страница 36: ...36 ...

Страница 37: ...37 ...

Страница 38: ...38 ...

Страница 39: ...39 ...

Страница 40: ...40 ...

Отзывы: