The installation of the SG850 probe, its ordinary and extraordinary
maintenance, and  its out of service removal  at  the end of the
functional life guaranteed by the manufacturer, must be carried
out by authorized or specialized personnel.

The general test should be performed by issuing gas from a pre-
calibrated aerosol within the percentages illustrated on the side.

Important: 

This test must be carried out at least once a year.

Test  after  replacing  the  sensor.

Reconnect  the  power,  the  probe  starts  blinking  to  the  waiting  time  (Warm-up).
After  waiting  you  can  proceed  to  test  the  functioning  inputting  the  sample  gas.
WARNING !!  From  this  moment  on  for  all  the  duration  of  24  hours  of  self-calibration,  the  probe  must  stay  in
clean  air  without  loss  of  GAS.

The  probe  continues  to  blink  at  a  low  frequency  again  for  24  hours  to  make  sure  that  the  probe  do  the  auto
calibration.

1) Put out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station and inform
the operators that you could have been poisoned by 

OXYGEN

 by an excess or deficiency of oxygen, or Carbon

dioxide

Gas

TEST  SG850

Probe with sensor                 Probe with sensor

                 Sensor

       Probe with sensor

to be raplaced

    removed

       remounted

Maintenance and gas sensor replacement

Before performing this operation disconnect the power to the probe.

OX YG EN
At 18.0%  -  or at 22,5 %  ±2%

Carbon  dioxide
At 5%, 10,  15,  20%   ±2%

WARNING! A

CTIONS

 

TO

 

BE

 

TAKEN

 

IN

 

CASE

 

OF

 

ALARM

Gas Input Test

Содержание SG850

Страница 1: ...AT industrial control unit or in stand alone mode detects the presence of Oxygen Carbon Dioxide SG850 O2 FOROXYGEN DETECTION This sensor through an optical fluorescence technology based sensor detects the presence of Oxygen O2 With this probe it is possible to 1 SELECT THE ALARM INTERVENTION FOR OXYGEN EXCESS OR DEFICIENCY 2 SELECT THE POSITIVE SAFETY OF THE RELAY SG850 CO2 FOR CARBON DIOXIDE DETE...

Страница 2: ... 100x100x60 CHECK the integrity of the unit after having removed it from the box Check that the data written on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible da...

Страница 3: ...dition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel Side view 60 mm Compatible control units Only Oxygen CONTROL UNITS MOUNTING PROBES Max DEGREE PRE ALARMS POSITIVE OPERATING protec alarms safety range GS300 Mc unit 1 zone Wall cabinet 3 IP44 2 1 YES NO BX444 MC unit 1 zone Wall cabinet 4 IP...

Страница 4: ...oor Light medium gas volatile The probe should not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Page 4 0 18 5 19 5 20 9 22 5 23 5 25 0 vol 0 4 15 8 16 5 17 4 18 4 19 ...

Страница 5: ...age at the terminals 1 2 It must be higher than 11Vdc and lesser than 25Vdc Check the voltage at the terminals 2 3 It must be from a minimum of 0 8 Vdc to a maximum of 1 1 Vdc If other problems arise the Distributor of BEINAT S r l should be contacted directly Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC Voltmeter Power Supply 12 24 V WARNING These measurement should be performed in clean air More...

Страница 6: ... Fault Operating LEDs IMPOSTAZIONI ALLARMI MICRO INTERRUTTORI n 2 n 3 5 OFF OFF 10 OFF ON 15 ON OFF 20 ON ON SWITCH 1 Positive safety Position ON Positive security enabled Position OFF Positive security disable WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the s...

Страница 7: ...nder tap 3 Do not turn any lights on or off do not turn on any electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department ...

Страница 8: ...ts in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natural reso...

Отзывы: