1)  “Power  connected”  LED,  thermostat  working.
2)  A uto mat ic/ Ma nua l  S wit ch  f or   sa nit ar y   h ot  wat e r
integration.
AUTOMATIC. By setting the switch up, you select the automatic
functioning.
a)  Automatic.  functioning  works  according  to  the  tempera-
ture  set  using  the  graduated  knob  from  30°C  to  80°C.  Please
see  point  No.  4
b) Manual. By setting the switch  down, you  select the manual
functioning.
When  selecting  the  manual  functioning,  the  integration  is
always  ON.
3)  Forced  pump  insertion  switch,  between  boiler  and
panel.
By  setting  the  switch  down,  you  select  to  forcedly  insert  the
circulation  pump  between  panel  and  boiler.
4)  Temperature  selection  knob.  It  is  used  to  set  the
desired  sanitary  hot  water  temperature  before  activation  of
the  integration.
5)  DELTA  T  knob  on  the  panel.  It  is  used  to  program  the
temperature  difference  between  BOILER  and  PANEL.  It  was
set  to  5°C  in  the  factory.

Electrical  connection  of  the

terminal  block  at  the  bottom

The  immersion  probes  can  be  inverted  one
with  the  other both  for position  and  polarity
Max. distance 150 m, with minimum diameter
of  1  mm

2

Electrical  connections

C

N C

NO

1     2     3     4     5     6

C

N C

NO

Pump
Connection

Integration
Connection

Power  Supply

230  VAC

Electrical  connection  of  the

terminal  block  at  the  top

The  relays  schematized  are  free
voltage  with  a  capacity  of  10  A
resistive.

1      2     3     4    5     6

S 1

S 2

S 3

Panel
probe

Boiler  H

2

O

integration
sensor

Boiler  H

2

O

accumulation
sensor

If the device  does not turn on:  Check  that  all  the  230V  cables  are
firmly  connected  the  terminal  block’s  poles  1  and  2.  Check  if  the
mains  power  supply  is  present.

The  control  unit  works  well  but  cannot  drive  the  appliances:
Check  that  all  the  wiring  is  correct.Please  remind  that  all  relays  are
free  of  voltage.Check  that  the  resistive  values  are  right.  Please  see
table  on  the  side.

If  other  problems  arise,  a  specialised  and/or  authorised  technician
and/or  the  Distributor  of  BEINAT  S.r.l.  should  be  contacted  directly.

Before  calling  a  technician,  check...

WARNING
Before  connecting  to  the  mains  power,  ensure  the  voltage  is  correct.
Carefully  follow  the  instructions  and  the  connections  according  to  Regulations  in  force,  keeping  in
mind  that  the  signal  cables  should  be  laid  separate  from  the  power  cables.
An  automatic  cut-off  switch  (appropriately  identified  as  devicesectioning  of  the  detector)  should
be  incorporated  in  the  electrical  system,  adequatelylocated  and  easily  accessible.

SC100/3  Components  and  Commands

Temp.  Resistive Temp.    Resistive
            values                   values

    0°C     155.820      10°C      94.523

30°C         37.704      40°C      24.695

50°C         16.533      60°C      11.296

70°C          7.865    80°C        5.573

95°C           3.427    100°C        2.936

SENSORS
Conversion  from  temperature
to  ohmic  value  of  the  probes

Содержание SC100

Страница 1: ...rential that varies from 1 to 9 C and can be regulated using the knob on the thermostat front panel Thanks to the 3 module Omega type format you can build several systems exploiting the modularity of the DIN rail in the previously set electrical panels Important Assembly maintenance of the appliance must be carried out by qualified personnel and in accordance with applicable laws and regulations T...

Страница 2: ...m plated weatherproof case art ST400 Power supply 230V 10 50Hz Power demand 1 VA Relay Contact Range 10A 250V resistive 5A 30V resistive Free of voltage contacts Type of sensors NTC 47K Functioning temperature sensors 20 C to 120 C Accuracy 1 C Resolution 1 C Delta differential temperature Adjustable from 0 C to 9 C Integration temperature Adjustable from 30 C to 80 C Integration Switch Automatic ...

Страница 3: ...nnection of the terminal block at the top The relays schematized are free voltage with a capacity of 10 A resistive 1 2 3 4 5 6 S 1 S 2 S 3 Panel probe Boiler H2 O integration sensor Boiler H2 O accumulation sensor If the device does not turn on Check that all the 230V cables are firmly connected the terminal block s poles 1 and 2 Check if the mains power supply is present The control unit works w...

Страница 4: ...l functioning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over t...

Отзывы: