Page  5

Components and Commands continue

11)  DISPLAY.  The  display  below  is  represented  with  all  its  segments  and  indications

a)  The  number  on  the  display  indicates  the  concentration  of  gas  detected.
b)  The  number  drawn  on  the  display  indicates  which  probe  is  monitored
The  exchange  of    data  of  every  connected  probe  is  every  about  4  seconds.
c)  The  letters  ppm  means  when  the  connected  probe  detects  toxic  gas.
The  letters  LEL  means  when  the  connected  probe  detects  explosive  gas.
d)  The  timing  symbol
  lights  when  the  control  unit  is  in  warm  up  phase,  the  same  time  its  begins  the  count
down.

c

000

a

d

LEL
ppm

1    2    3

b

IMPORTANT  NOTE
The  installation  of  the  detector  is  not  exempt  from  ...…  The  compliance  with  all  regulations  concerning  the  characteristics,
installation  and use  of  gas  appliances.  The  ventilation of  the  spaces and  the  elimination  of  combustion  products are  described
in the  UNI  norms  according  to  ART.  3  LAW  1083  /  71  and  relevant  legal  provisions.

Description of Display

The  BX444Mc  is  equipped  with  a  display  backlight  color  to  facilitate  the  recognition  of  the  state  of  the  probe
monitored.
The  data  exchange  for  each  probe  connected  happens  every  4  seconds.

00

LEL

300

ppm

The  blu  display  shows
th e  

p e rce nta g e  

of

ox y g e n. 

n orm al

condition

20.6

%

20

LEL

FAU

Th e   g re e n   d i sp l ay
shows  an  absence  of
leakage  of  gas,  normal
conditione

The  display  shows  with
red  color  a  concentration
of  explosive  gases  in
%  LEL  greater  than  a
threshold  alarm.

The  display  shows  with
red  color  a  concentration
of  toxic  gases  ppm
greater  than  a  threshold
alarm.

The  yellow  display  shows
a  fault  of  one  or  more
prob es.

<

19.9  %

>

21.9  %

<

19.5  %

>

22.5  %

<

18.5  %

>

23.5  %

1st Pre-Alarm

2nd Pre-Alarm

Main alarm

< Oxygen deficienty
> Excess Oxygen

The  BX444-Mc  presents  three
levels  of  danger  which  are:

Содержание GS300-Mc

Страница 1: ...all underground car parks The GS300 Mc control unit has three danger levels 1st LEVEL 1st Alarm This was set to 8 of L E L 120ppm 2nd LEVEL 2nd Alarm This was set at 13 of L E L 200ppm 3rd LEVEL Main Alarm This was set at 20 of L E L 300ppm For oxygen the centrol unit GS300 Mc presents three levels of danger which are 1st Pre Alarm Both in deficiency and excess of Oxygen 2nd Pre alarm Both in defi...

Страница 2: ...h Battery Max 2 2 Ah Optional 12 V 10 Battery Charger max 2 2 Ah Controlled Power Demand 8 3W max 230V Power Demand 4W max 12V Relay Contact Range 10A 250VAC resistive 5A 30Vdc resistive 1st Pre Alarm Set to 8 of L E L or 120ppm CO 2nd Pre Alarm Set to 13 of L E L or 200ppm CO Final Alarm Set to 20 of L E L or 300ppm CO Monitored Gas Indication Through backlit color display Number of Conventional ...

Страница 3: ...one 2 Oxygen In 4 20 mA 5 Yes Yes SGF106 SemiCondut IP64 Zone 2 FREON 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Elettrochimica IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone ...

Страница 4: ...r 300ppm ref CO and the MAIN ALARM relay contact is closed The buzzer will issue a high frequency sound 10 FAULT LED This LED blinks when one of the connected probes is faulty if there is an interruption in the cable connection or if an error was made during wiring When this LED is blinking the device is no longer capable of detecting To reactivate the device the damaged probe must be repaired or ...

Страница 5: ...s appliances The ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 1083 71 and relevant legal provisions Description of Display The BX444Mc is equipped with a display backlight color to facilitate the recognition of the state of the probe monitored The data exchange for each probe connected happens every 4 seconds 00LEL 300pp...

Страница 6: ... from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible Electrical Connections Power supply 230 VAC PH N 4 5 6 7 8 9 10 11 12 C NC NO C NC NO C NC NO C NC NO Fault 1st threshold 2nd threshold Main alarm PLEASE NOTE All relays are free of voltage Connection...

Страница 7: ... 7 8 9 10 11 12 Power supply 230 VAC C NC NO C NC NO C NC NO C NC NO Fault 1 Threshold 2 Threshold Alarm Solenoid valves Ph N PH N 4 5 6 7 8 9 10 11 12 Power supply 230 VAC C NC NO C NC NO C NC NO C NC NO Fault 1 Threshold 2 Threshold Alarm Solenoid valve Connection examples Power supply 230 12V Diode 1N 5406 3 2 1 Probe 1 3 2 1 Probe 2 3 2 1 Probe 3 Solenoid valve GAS and Sirens 12 VDC 1 2 3 4 5 ...

Страница 8: ...ay and is maintained for 15 seconds On the next pass the LED probe will be maintained again and the alarm will be issued In case of fault The LED of the relevant probe starts blinking and remains lit The display will show the FAU Fault fixed indication and the buzzer will issue a continuous sound until 1 The repair has been carried out 2 The relevant probe has been disabled using the micro switch ...

Страница 9: ...ed The relay is energized after performing the waiting phase and switches when the GS300 Mc is in main alarm In the OFF position the positive safety function is disabled The relay is energized only when the GS300 Mc enters the state of main alarm Switch 2 Functioning Mode of main alarm relay In the ON Continuous function the relay remains closed until the RESET button is pressed In the OFF Impulse...

Страница 10: ...ition of the detection sensors You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest p...

Страница 11: ... the 240VAC mains power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the probe cables are connected as in the drawing they have not pinched the insulating sheath Check that the voltage at the terminals 3 4 is greater than 11 VDC and less than 25 VDC Check that at the terminals 3 and 5 6 7 is present a volta...

Страница 12: ...LECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local r...

Отзывы: