GN-9212 User Manual
Page 9 of (54)
G-series GN-9212 DeviceNet Rev. 1.01.docx
2.3. Device Net Specification
Items
Specification
Communication Interface Specification
Adapter Type
Group 2 Only Slave
Max. Expansion Slot
63 Slots
I/O Data Size
Max 128 bytes each slot
Max. Length Bus Line
Max.100m@500Kbps, Max. 250m@250Kbps, Max. 500m@125Kbps
Max. Network Node
64 Nodes
Baud Rate
125Kbps(Max. 500m)
250Kbps(Max. 250m)
500Kbps(Max. 100m)
Protocol
Poll, Bit-Strobe, Cyclic, COS
Node MAC ID Setup
DIP Switch
Terminating Resistance Setup
DIP Switch
Bus Connection
5 Pin Open-Style Connector
Other Serial Port
RS232 for MODBUS/RTU, Touch Panel or IOGuide
Serial Configuration (RS232)
Node
:
1 (Fixed)
Baud Rate :
115200 (Fixed)
Data bit
:
8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit
:
1 (Fixed)
Indicator
6 Status LEDs
1 Green/Red, Module Status (MOD)
1 Green/Red, Network Status (NET)
1 Green, TerminatingResistance Status (TER)
1 Green/Red, Expansion I/O Module Statsus (IOS)
1 Green, System Power Status
1 Green, Field Power Status
Module Location
Starter module left side of G-Series system
Field Power Detection
About 14Vdc