![Beijer Electronics DeviceNet G Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/beijer-electronics/devicenet-g-series/devicenet-g-series_user-manual_2723543028.webp)
GN-9212 User Manual
Page 28 of (54)
G-series GN-9212 DeviceNet Rev. 1.01.docx
5.5.3. DeviceNet Object
Common Services
Service
Code
Implemented for
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave_Connection_Set
0x4C
No
Yes
Release_Master/Slave_Connection_Set
Class Attributes
Instance
ID
Attribute
ID
Access
Rule
Name
Data
Size
Value
0
1
Get
Revision
1 word
02, 00
Instance Attributes
Instance
ID
Attribute
ID
Access
Rule
Name
Data
Size
Value
1
1
Get/Set* MAC ID
1 byte
0 ~ 63
2
Get
Baud Rate**
1 byte
0=125K, 1=250K, 2=500K, 3=Auto
3
Get/Set
Bus off Interrupt
BOOL
faulted node recovery,
(0x01 : Enable)
4
Get
Bus-Off Counter
USINT
0 ~ 255
5
Get
Allocation
Information
- Allocation Choice
- Master's MAC ID
Structure
of:
BYTE
USINT
- Allocation Choice
Defined in Spec.
- Master’s MAC ID
255: unallocated
0~63: Master MAC ID
8
Get
MACID
Switch
Value
USINT
0 ~ 99
Actual value of Switch
9
Get
Baud Rate Switch
Value
USINT
0 : 125kbps
1 : 250kbps
2 : 500kbps
3 : Auto
Class Code: 03
HEX