Additional Installation Tips

A good solution may be to use a shielded Ethernet cable, but to connect the shield
at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernet cable, see 4 in drawing above.
The shield can be grounded via an external 0.1 μF/250 V film capacitor, see 5 in
drawing above. This connects the HF transients to ground.

6.3 To Achieve Better EMC Protection

Initially, use the original cabling from Beijer Electronics primarily.

Use shielded cables for RS-232 communication.

Use twisted pair and shielded cabling for RS-422 and RS-485.

Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link,
CAN, Device Net etc.

Install and connect according to applicable specifications for the relevant bus
standard.

Use shielded cabling for Ethernet, preferably with foil and a braided shield.

D-sub covers should be shielded, and the shield should be connected to the
cover 360° where the cable enters.

Connect the shield at both ends.

Shielded cable

Not same potential

Ground plane 1

Ground plane 2

Ground plate

Ground plate in another building

0.1 

μ

F/250 V

With longer distances, there is a risk that the ground potential may be different. In
that case, the shield should only be connected at one end. A good alternative is to
connect the other end of the shield to the ground via a 0.1 μF/250 V film capacitor.
Both ends are then connected to the ground in terms of HF, but only connected to
the ground at one end in terms of LF, thus avoiding the 50/60 Hz grounding loops.

Metal cabinet

Metal cabinet

Terminal or connector

Terminal or connector

EMC cable gland

Plastic cable gland

Shielded cable

Short distance

Cable clamp
in steel

Shielded cable

1. Use an EMC cable gland or regular plastic cable gland, remove the outer jacket

and connect the shield to the installation plate with a 360° metal cable clamp.

Beijer Electronics, MAEN274

23

Содержание BoX2 extreme

Страница 1: ...BoX2 base Installation Manual English MAEN274 2018 03...

Страница 2: ......

Страница 3: ...ts group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only quali ed personnel ma...

Страница 4: ...Foreword Beijer Electronics MAEN274...

Страница 5: ...ions to the Controller 12 2 1 2 Other Connections and Peripherals 13 3 TechnicalData 15 4 ChemicalResistance 17 4 1 Plastic Casing 17 5 Operator Panel Drawings 19 5 1 Connectors 19 5 1 1 Communication...

Страница 6: ...Contents Beijer Electronics MAEN274...

Страница 7: ...ier cannot assume responsibility for actual use based onthe gures The supplierneither guarantees thatthe operator panel is suitable foryour particularapplication nor assumesresponsibilityforyour produ...

Страница 8: ...tion All deviceshave tobe supplied bya Class 2 powersupply Warning Only UL and cUL approved expansion units are allowed to be connected to the port designated EXPANSION At the moment there are no such...

Страница 9: ...blecontrollers industrialPCs forthe use in industrial controlequipment and are intended to be front panel mounted Type 12 and4x forindoor use only Caution The enclosure provides a degree of protection...

Страница 10: ...uali ed personnel shouldcarry outrepairs The agreed warranty applies Before carryingout any cleaningormaintenance operations disconnect the equipment from the electrical supply 1 8 Dismantling and Scr...

Страница 11: ...lipped onto aDIN rail The followingis needed Notools required standard usage 1 Unpackand check the delivery If damage isfound notify the supplier Note Place the operator panelon a stable surface durin...

Страница 12: ...and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables are recommended 24V DC RS232 RS422 RS485 24V DC A D Controller Power...

Страница 13: ...er Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier Beijer...

Страница 14: ...Installation 14 Beijer Electronics MAEN274...

Страница 15: ...M N A Real time clock Yes Battery Lithium ion 3V 200 mAh Power consumption at rated voltage 3 W Fuse Internal DC fuse 2 0 AT Power supply CE The power supply must conform with the requirements accordi...

Страница 16: ...Technical Data 16 Beijer Electronics MAEN274...

Страница 17: ...cid 10 The material shows limited resistance to the followingchemicalsat room temperature Cleaner s naphtha free from aromatic hydrocarbons Heatingoil Ethyl alcohol 96 Isopropanol Glycerin N hexane Gl...

Страница 18: ...Chemical Resistance 18 Beijer Electronics MAEN274...

Страница 19: ...se T shielded RJ45 4 COM B Serialcommunication port 5 1 1 Communication Ports Serial port 9 pin female Serial port 9 pin female Pin COM 1 COM 2 COM 3 COM 4 1 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx...

Страница 20: ...Operator PanelDrawings 5 2 BoX2 base Outline 35 130 89 Note A Step CAD file is available on the web site www beijerelectronics com 20 Beijer Electronics MAEN274...

Страница 21: ...terminalconnectoron the operatorpanel and the chassis of the panel see 2 in drawing above 2 Connect awire orgroundingbraid that is sized correctlyaccording to local electrical codes betweenthe chassi...

Страница 22: ...RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 F 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45 c...

Страница 23: ...withfoil and abraided shield D sub covers shouldbe shielded andthe shield shouldbe connected to the cover 360 where the cable enters Connect the shield at both ends Shielded cable Not same potential G...

Страница 24: ...e are anumberofheat generatingdevices the temperature at the top ofthe cabinet is considerably higherthan the temperature increase that would be expected All electronics are sensitive to heat The life...

Страница 25: ...tion against electric shock and UL 950 Note Here is an example that explains why a secure 24 V DC powersupply can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller cont...

Страница 26: ...gged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial risk of problems Groundingcurrents go through commu...

Страница 27: ...e shield mustbe grounded at one end The other end is usuallygrounded but with longerdistances or whenthere is adifference in the ground potential the shield should be connected tothe ground via 0 1 F...

Страница 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Отзывы: