4.7 EMC-filter
BFI contains an internal EMC-filter connected to earth. BFI with built-in EMC-filter must never be
used in systems were the 3-phase supplying net don’t have a neutral connected to earth, normally
called IT-net. The BFI can be damaged. IT-net is normally being used in all types of boats and also
some parts of Norway.
In the rest of Europe TN-net is most common were EMC-filter can be used.
The EMC-filter of IP20 and IP66 are disconnected according to the pictures below. Remove the
screw/screws marked “EMC”, see arrows in the picture below.
IP20
Size 1 to 3
IP20
Size 4
IP20 Size 5
All IP66
4.8 IP66, Main switch, start/stop switch and potentiometer
By adjusting the parameter settings, the drive can be configured for multiple applications and not just
for Forward or Reverse. This could typically be for Hand/Off/Auto applications (also known and
Local/Remote) for HVAC and pumping industries.
Switch Position
Parameters
to Set
Notes
P-12
P-15
Run Reverse
STOP
Run Forward
0
0
Run Forward or Reverse – Speed reference Local Pot
STOP
STOP
Run Forward
0
5,7
Run Forward – Speed reference Local Pot
Run Forward /
Preset Speed 1
STOP
Run Forward /
Local Pot
0
1
Preset Speed 1 is set in parameter P-20
Run Reverse
STOP
Run Forward
0
6, 8
Speed reference Local Pot. See terminal 4 function.
Run Forward / AI1
STOP
Run Forward / AI2
0
4
AI1 is normally the Local Potentiometer.
Run Forward / AI1
STOP
Run in PI Control
5
1
AI1 is normally the Local Pot.
In PI Control, Local Pot is PI set point if P-44=1.
Run Forward /
Preset Speed 1
STOP
Run in PI Control
5
0, 2, 4, 5,
8..12
Preset Speed1 is set in parameter P-20.
In PI Control, Local Pot is PI set point if P-44=1.
Run Forward /
Local Pot
STOP
Run / Fieldbus
3
6
Speed reference by CANopen eller Modbus TCP och
Modbus RTU. Sign of set speed decide direction.
Run Forward /
Preset Speed 1
STOP
Run / Fieldbus
3
3
Speed reference by CANopen eller Modbus TCP och
Modbus RTU. Sign of set speed decide direction.