16
Technical Description
Menue lines
Menue line ‚A‘
A 5 0 , 0 1 0 0 , 0 7 , 5
Set-point value2 Set-point value1 Measured current
In Menue line ‚A‘ the two set-point values as well as the measured current (in A) are
displayed. The set-point values can be set in 0,5% steps between 0,0% and I-MAX
(see Menue line ‚B‘). This directions refer always to the set output current range (see
DIP-Switch S12.6). The set-point value 2 is only displayed if it has been released by
switch S12.5. The changeover between set-point value 1 and 2 is done by Input X13.
If this input is selected, set-point 2 is active, otherwise set-point1.
Menue line ‚B‘
B 0 5 0 % = 1 , 2 A 2 , 5 A
Maximum current
Current range
In menue line ‚B‘ the maximum output current can be limited. Through that, the
connected feeding device can be protected from overloading. Furthermore, the
current range set with DIP-Switch S12.6 is displayed.
Attention: In this menue the value can only be changed by actuating DIP-Switch
S12.4.
Menue line ‚C‘
C f = 1 2 0 , 4 H z
Set frequency
In this menue the output frequency is displayed resp. adjusted. An adjustment
between 10,0 and 150,0 Hz is possible.
Menue line ‚D‘
D T 0 1 = 2 , 0 1 , 0
Soft start
Soft run-out
In Menue line ‚D‘ the soft start and soft run-out can be set. Values between 1,0 and
5,0 seconds are possible.