When connecting to a voltage >120V AC the glow
lamps are illuminated for phase control purpose.
"
Press button ON (6). The green LED indicates that
the instrument is ready for testing.
"
If the LED R (3) is illuminated, a clockwise rotary
field is present. If the LED L (4) is illuminated, a
counter-clockwise rotary field is present.
The phase control is displayed even if the neutral
conductor N is connected instead of L1, L2,or L3.
Imperatively verify correct phase connection car-
rying out a bipolar test using a voltage tester, e.g.
UNITEST 2000 alpha.
Also refer to table (as indicated on the instrument
rear)
6.0 Contact-free rotary field determina-
tion
Remove connected test leads to avoid injuries
caused by entanglement into rotating parts.
The safety measures of accident prevention reg-
ulations regarding the work with rotating machines
must be fulfilled!
The UNITEST M-Indicator allows the contact-free ro-
tary direction determination of a running synchronous
or asynchronous three-phase motor.
Determination of the Rotary Field
19
English
Phasenanzeige
Drehfeldrichtung
DF richtig
DF falsch
L1 fehlt
L2 fehlt
L3 fehlt
nicht definiert
Aus
An
Phase indication
Phase rotation
rotat. right
rotat. left
L1 missing
L2 missing
L3 missing
not defined
Off
On
Содержание UNITEST M-Indicator 9062
Страница 13: ...UNITEST Instruction Manual Cat No 9062 Mode d emploi Réf 9062 Manual de Instrucciones Art No 9062 M Indikator ...
Страница 14: ......
Страница 26: ...26 ...
Страница 27: ...UNITEST Mode d emploi Réf 9062 Manual de Instrucciones Art No 9062 M Indikator ...
Страница 37: ...UNITEST Manual de Instrucciones Art No 9062 M Indikator ...
Страница 38: ...38 ...
Страница 50: ...50 ...
Страница 52: ...52 10 2000 PTDB9062 02 ...