10
Power-On Options
To select a power-on option, press and the function key simultaneously and then release
the button. Power-on options are retained when the tester is turned OFF. See Table below.
UK - Mode Selected
Automatic Lead
Swapping Mode Selected
Figure 2. Lead Swapping Modes
Keys
Power-on Options
Loop/Line Impedance I
K
limit. Toggles the I
K
limit between 10 kA and 50 kA.
The default is 10 kA.
Line and Neutral Swap mode. Two modes of operation are available. You
can configure the tester to operate in L-n mode or L-n n-L mode,
• In L-n mode, the L and N phase conductors must NEVER be reversed.
This is a requirement in some regions including the UK. The
icon
appears on the display indicating that the system L and N conductors are
swapped and testing is inhibited. Investigate and rectify the cause of this
system fault before proceeding. L-n mode also changes the RCD x1/2 trip
time duration to 2 seconds as required in the UK.
• In L-n n-L mode, the unit allows the L and N phase conductors to be
swapped and testing will continue.
Note: In locations where polarized plugs and outlets are used, a swapped
lead icon (
) may indicate that the outlet was wired incorrectly.
Correct this problem before proceeding with any testing.
Fault voltage limit. Toggles the fault voltage between 25 V and 50 V. The
default is 50 V.
Continuity beeper toggle. Toggles the continuity beeper on and off. The
default is on.