A–25
Appendix – A
Figure A-8 Configuration Screens (page 4 of 8)
Configuration/Mtr Current Profile (Cont'd)
Duration % Change
xxx
Setting for Duration current programmable from 10% to 200%
of the stored Duration current to activate an alarm.
Init. Motor Current
Press ENT to reset.
Allows the user to reset all Motor Current Profiles and initiate
the "Training Mode".
Configuration/CBEMA Setup
Normal Voltage
xxx.x Volts
This parameter establishes the target voltage around which the
Event settings determine "Sag" or "Swell" conditions.
Event 1 (2, 3, 4)
ENABLE
Enables/Disables CBEMA Event 1, 2, 3 or 4.
Event 1 Sag Pickup
xx %
When pickup is set to less than 100% it operates as a Sag
(undervoltage), greater than 100% it operates as a Swell
(overvoltage).
Event 1 Sag Dropout
xx %
Sag Dropout is always set greater than Sag Pickup. Swell
Dropout is fixed at 100%.
Event 1 Min Dur
x Cycles (xx ms)
Establishes the minimum duration that Sag or Swell condition
exists before an Event is registered.
Clear All Counters
Ready Press ENTER
Clears all CBEMA Event Counters.
Configuration/Harmonics Setup
V 2-16 Har. Alarm
011111111111111
Provides the user with the means to select active harmonics for
voltage alarm 2-16.
V 17-31 Har. Alarm
000000001010101
Provides the user with the means to select active harmonics for
voltage alarm 17-31.
V Alarm Threshold
10.0 %
Allows the user to select the Harmonic Voltage Alarm Threshold
value.
Event 1 (2, 3, 4) Sag (Swell)
Event 1 (2, 3, 4) Sag (Swell)
Event 1 (2, 3, 4) Sag (Swell)