FUNCTION
AVAILABLE RARGES
ACCURACY
1 . Undervo1tage
2 . Overvoltage
3 . Under Frequency
4 . Over Frequency
5.
Undervoltage Trip Tirner*
6 . Overvoltage Trip Tirner*
7 . Under Fr equency Trip Timer*
8 . Over Frequency Trip Timer*
9 . Reconnect Tirner*
NOTE:
9 7% , 96% , 9 5% ,9 4% ,90% , 85% , 80% of 1 20 V
103% ,104% , 105% , 106% , 1 10% , 1 15% , 1 20% of
59 .9 t o 55 Hz in 0 . 1 Hz increments
60 . 1 to 6 5 Hz in 0 . 1 Hz increments
1 to 9 9 99 cycles in 1 cycle increments
1 to 9999 cycles in 1 cycle incr ements
1 to 9 9 99 cycles in 1 cycle inc r ements
1 to 9999 cycles in 1 cycle increments
0 to 1092 sec in 1 sec increments
:1:2%
1 20 V :1:2%
:1:.02
:1:.02
**
**
**
**
***
*
The time delay specif i e d is an i n t e n tional d e l ay added to t h e inhe r ent
m e a s u r e m e n t time o f the P RIDE @ R e l a y. The t o t a l t i m e d e l ay f o r t ripp i n g or
r e c l o sing i s the s u m o f the appr opria t e d e l ay a s spec i f ied in 5 , 6 , 7, 8 o r
9 pl u s the m e a s u r e m ent time o f the unit. The m ea s u r e m e n t t i m e de lay i s
dependent oh the input conditions. The M -0 2 90 voltage m e a s u r e m e n t t i me
d e l a y , f o r a l o s s o f inp u t , can v a r y f r o m 3 t o 6 cycles f o r u n d e r v o l t a g e
settings of 95% to 80% .
**
V a l u e i n cyc l e s is b a s e d on an
i n t e rnal 60 H z timer
a c c u r a t e to
1 / 2
cycle o r ±l% of setting, whichever is greater (refer t o note * above).
*** Value in seconds is based on an internal 60 Hz timer accurate to 1 / 2 second
or ±l% of setting, whichever is greater (refer to note * above).
DSER ADJUSTMENTS
Hz
Hz
In order to provide
a
mJ.n1mwn cost system, the
PRIDE
Relay is available without user adjustments for
the nine functions listed above. The desired limits for these functions must be spe cified on the
purchase order. The set!Xlints for all but the Undervo1tage or OVervoltage function may
be
changed at
any time by addition of an optional M-0297/M-0397 Field Adjustment Unit which is easily installed by
the user. (The Undervo1tage or OVervoltage set!Xlints may
be
changed through a minor hardware modifica
tion) . The Field Adjustment Unit can also be used to monitor conditions such as line frequency and
timer progress, to enable certain fLmctions,
as
well
as
interrogating setpJints or trip targets.
When ordering the PRIDE Relay
ldth
the Field Adjustment Unit, the user must specify a set of fixed
backup settings that will
be
used if the M-0397 is later removed from the PRIDE.
If the optional M-0297/M-0397 Unit
� nQt
purchased and the user wishes to change PRIDE settings, the
old Memory Board model M-0298 containing the settings can be exchanged for a new one that can be
installed by the user. Alternatively, additional Memory Boards are available separately from the
factory.
POWER INPUT
Ac Supply: 80 to 1 40 V ac, 60 Hz :1:10 Hz. 20 W max. will withstand 1 70 V ac for 5 sec.
Dc
S
u
pp
l
y
:
Nominal input voltage 125 V dc, 48 V dc, or 24 V dc; 25 W max. The PRIDE will operate from
awroximate1y 65% to 128% of the nominal input voltage
and
will withstand 150% of nominal voltage for 5
sec. Operation from 250 V dc is posSible, but requires the external M-0319 Dropping Regulator
Optioo
to provide 125 V dc nominal input voltage to the
PRIDE.
CAPACITOR POWER HOLD-UP OPTION
Provides power for operation of
Ac
Supply PRIDE Units for up to 3 sec after loss
of
input power.
SENSING INPUT
o
to 160 V ac at 60 Hz:l:15 Hz. 1 W maximum.