Technical data, mounting, wiring
PS3011-2440-0000
19
Version: 1.0
3.10
Efficiency and losses
AC 100 V
AC 120 V
AC 230 V
Efficiency
Typ.
93.2%
93.6%
94.6%
At 24 V, 40 A
Average efficiency
*)
Typ.
92.7%
93.0%
93.9%
25% at 10 A, 25% at 20 A,
25% at 30 A. 25% at 40 A
Losses
Typ.
3.6 W
3.5 W
3.3 W
With activated shutdown
Typ.
13.9 W
13.1 W
13.2 W
At 24 V, 0 A (no load)
Typ.
36.1 W
34.5 W
30.6 W
At 24 V, 20 A (half load)
Typ.
70.0 W
65.6 W
54.8 W
At 24 V, 40 A (nominal load)
*)
The average efficiency is based on assumptions for a typical application with a power supply load of:
25% of the nominal load for 25% of the time,
50% of the nominal load for 25% of the time,
75% of the nominal load for 25% of the time and
100% of the nominal load during the remaining time.
Fig. 12: Efficiency over output current; losses over output current
Fig. 13: Efficiency over input voltage; losses over input voltage