Protective functions and safety features
Protective functions
Output overvoltage protection
Typ. 31.5 Vdc
Max. 34 Vdc
In the event of an internal power supply fault, a redundant circuit limits
the maximum output voltage. In such a case the output switches off
and automatically attempts to restart.
Protection class
IP20
EN/IEC 60529
Overtemperature protection
Yes
Output shutdown with automatic restart.
Temperature sensors are installed on critical components inside the
device and switch off the device in safety-critical situations. This can
happen, for example, if the ambient temperature is too high, ventila-
tion is obstructed or derating requirements are not met. There is no
correlation between the operating temperature and the switch-off tem-
perature, as this depends on the input voltage, the load and the instal-
lation methods.
Protection against
input transients
MOV (metal oxide varis-
tor)
For further information see
chapter
Input fuse
Included
Slow-blow fuse, not user-replaceable, with high braking power
Safety features
Insulation resistance
Min. 500 MOhm
In the delivery state between input and output,
measured with 500 Vdc
Min. 500 MOhm
In the delivery state between input and PE (Protective Earth),
measured with 500 Vdc
Min. 500 MOhm
In the delivery state between output and PE,
measured with 500 Vdc
Min. 500 MOhm
In the delivery state between output and DC-OK contacts,
measured with 500 Vdc
Protection class
I
According to IEC 61140
PE (protective conductor) connection required
Touch current (leakage current)
Typ. 0.35 mA / 0.73 mA
At 230 Vac, 50 Hz, TN, TT / IT network
Max. 0.46 mA / 0.97 mA
At 264 Vac, 50 Hz, TN, TT / IT network