Technical data, mounting, wiring
PS1061-2410-0000
17
Version: 1.0
3.6
DC-OK relay contact
This function monitors the output voltage generated by the power supply itself.
The contact closes
when the output voltage reaches 22 V.
The contact opens
as soon as the output voltage falls below 22 V.
Switching hysteresis
not included
Contact load capacity
Maximum 60 Vdc 0.3 A, 30 Vdc 1 A, 30 Vac 0.5 A, ohmic load
Minimum permissible load: 1 mA at 5 Vdc
Insulation voltage
Fig. 6: Behavior of the DC-OK relay contact