background image

M2510  Analog Input 

Beckhoff II/O Lightbus System 

Date:

 20.08.93 

Version :

 2.0 

Page

 11 

of 11 

5. Connections Table 

Pin assignment with signal description 

 

Conector X10 

 

Connector Pin  Signal Description 

X10  

1  + 

Control power 24 V 

X10  

2  - 

ground 

 
 
 

Connector X20 

 

Connector Pin  Signal Description 

X20 

 1 

-15 V 

Support voltage -15 V DC  

X20 

 2 

+15 V 

Support v15 V DC, 24 V DC 

X20  

3 E1 

Analog input channel 1 

X20  

4 GND 

ground 

X20 

 5 

-15 V 

Support voltage -15 V DC  

X20 

 6 

+15 V 

Support v15 V DC, 24 V DC 

X20  

7 E2 

Analog input channel 2 

X20  

8 GND 

ground 

X20 

 9 

-15 V 

Support voltage -15 V DC  

X20 10 

+15 

Support v15 V DC, 24 V DC 

X20 11 E3 

Analog input channel 3 

X20 12 GND 

ground 

X20 13 

-15 

Support voltage -15 V DC  

X20 14 

+15 

Support v15 V DC, 24 V DC 

X20 15 E4 

Analog input channel 4 

X20 16 GND 

ground 

 

Содержание M2510

Страница 1: ...M2510 Analog Input Beckhoff II O Lightbus System Date 20 08 93 Version 2 0 Page 1 of 11 M2510 Analog Input Technical Description Eiserstraße 5 Phone 495246 963 0 33415 Verl Fax 495246 963 149 ...

Страница 2: ... Beckhoff II O Lightbus System Page 2 of 11 Version 2 0 Date 20 08 93 Table of Contents 1 Function Description Hardware 3 2 Function Description Software 5 3 Technical Data 6 4 Installation Notes 7 5 Connections Table 11 ...

Страница 3: ...10 V to 10V e 1 V to 1V can be used The resolution is 12 bit so that in a single telegram of the II O system parallel transmission of 2 ADU s is possible The whole module uses 2 addresses in the II O system There are four LEDs for system diagnosis Working normally only the green LEDs CYCLE XILINX1 and CYCLE XILINX2 are switched on In case an error is detected the red ERROR XILINX1 ERROR XILINX2 LE...

Страница 4: ...M2510 Analog Input Beckhoff II O Lightbus System Page 4 of 11 Version 2 0 Date 20 08 93 15V 15V 24V GND Ain 1 Ain 2 Ain 3 Ain 4 4 Analog inputs Basic circuit diagram ...

Страница 5: ...previous cycle is used There is no need for selection or other communications since all control signals needed are created by the hardware As there are always 2 ADCs read in a 32 bit telegram two addresses in the II O system have to be reserved for the whole module II O Lightbus Address 1 ADC 2 ADC 1 Port D3 Port D2 Port D1 Port D0 LSB DDDD DDDD DDDD DDDD MSB xxxx DDDD xxxx DDDD II O Lightbus Addr...

Страница 6: ...tbus System Transmission Rate 2 5 MBaud 25 µs for 32 bit Support Voltage Connection 15 V 80 mA total load short cirquit proof Option 24 V 15 V Supply Voltage 24 V DC 10 Input Current 0 17 A at 24 V DC without support voltage load Input Impedance 1 MOhm using unipolar voltage measuring 2 MOhm using bipolar voltage measuring 50 Ohm 500 Ohm measuring the current Cartridge closed cartridge can be inst...

Страница 7: ...astic fibres are used no special tools are needed for installation of the plugs The M2510 is installed at the machine or simply by installing it to a cartridge carrier according to DIN EN 50022 or DIN EN 50035 Configuration Before setting the system to work the desired modes of the Analog transformers have to be adjusted by setting certain jumpers according to the following configuration table Inp...

Страница 8: ...nput with ground read channel by II O Lightbus test program or other II O Lightbus software continuously to provide constant transformation use potentiometer Offset unipolar to adjust the value read to 0 connect and adjust precisely 1V to the input and then adjust by using potentiometer GAIN to the value FFFh c unipolar 0 20 mA connect input with ground read channel by II O Lightbus test program o...

Страница 9: ... or other II O Lightbus software continuously to provide constant transformation adjust by using potentiometer Offset bipolar the read in value to 800h connect and adjust precisely 1V to the input and then adjust by using potentiometer GAIN to the value 000h Spannungsversorgung There is a two pin terminal X10 Pin1 2 for the supply voltage with connections for control logic ...

Страница 10: ...Jumper J1 1 select operation mode Channel 1 X10 24V II O X20 4 1 FO transmitter FO receiver Connector X20 Connector X10 Control power supply 24V ground Poti G1 GAIN Poti BO1 Bipolar Offset Poti UO1 Unipolar Offset LD4 LED ERR2 XILINX2 LD3 LED CYC2 XILINX2 LD2 LED ERR1 XILINX1 LD1 LED CYC1 XILINX1 50 500 Ohm Switch over burden resistor Adjustment Channel 1 ...

Страница 11: ...15 V DC X20 2 15 V Support voltage 15 V DC Option 24 V DC X20 3 E1 Analog input channel 1 X20 4 GND ground X20 5 15 V Support voltage 15 V DC X20 6 15 V Support voltage 15 V DC Option 24 V DC X20 7 E2 Analog input channel 2 X20 8 GND ground X20 9 15 V Support voltage 15 V DC X20 10 15 V Support voltage 15 V DC Option 24 V DC X20 11 E3 Analog input channel 3 X20 12 GND ground X20 13 15 V Support vo...

Отзывы: