Access from the user program
KL3311, KL3312, KL3314 and KL3302
35
Version: 4.2
BK4000 Interbus Coupler
The BK4000 Interbus Coupler maps the terminals in the delivery state with 2 bytes per channel:
• KL3311: 2 bytes of input data
• KL3312 (KL3302): 4 bytes of input data
• KL3314: 8 bytes of input data
Parameterization via the fieldbus is not possible. If the control and status byte is to be used, the KS2000
configuration software is required.
Fig. 23: Mapping in the Interbus Coupler - example for KL3312, KL3302
Other Bus Couplers and further information
Further information about the mapping configuration of Bus Couplers can be found in the Appendix of the
respective Bus Coupler manual under
Master configuration
.
The chapter on Mapping in the Bus Coupler contains an overview of possible mapping configurations,
depending on the configurable parameters.
Parameterization with KS2000
The KS2000 configuration software can be used for parameterizations via the serial interface of the
Bus Coupler, independent of the fieldbus system.
5.2
Mapping in the Bus Coupler
As already described in the
Terminal Configuration
section, each Bus Terminal is mapped in the Bus
Coupler. This mapping is usually done with the default setting in the Bus Coupler / Bus Terminal. The
KS2000 configuration software or a master configuration software (e.g. ComProfibus or TwinCAT System
Manager) can be used to change this default setting.
If the terminals are fully evaluated, they occupy memory space in the input and output process image.
The following tables provide information about how the terminals map themselves in the Bus Coupler,
depending on the parameters set.