Product overview
KL3224
12
Version: 2.0.0
Resistance limit values
R > 400 Ω: Bits 1 and 6 (overrange and error bits) in the status byte are set. The linearization of the
characteristic curve is continued with the coefficients of the upper range limit up to the limit stop of the A/D
converter (approx. 500 Ω for PT100).
R<18 Ω: Bits 0 and 6 (underrange and error bits) in the status byte are set. The smallest negative number is
displayed (0x8001 corresponds to -32767).
For overrange or underrange the red error LED is switched on.
LED display
The LEDs indicate the operating state of the associated terminal channels.
Red LEDs: ERROR
• On: Short circuit or wire breakage. The resistance value is in the invalid range of the characteristic
curve.
• Off: The resistance is in the valid range of the characteristic curve.