Product overview
KL26xx/KS26xx
20
Version: 2.5.0
2.4.1
Technical data
Technical data
KL2634, KS2634
Number of outputs
4 make contacts (potential-free)
Contact material
Silver alloy (stationary contact gold-plated)
Rated load voltage
250 V
AC
/30 V
DC
Load type
ohmic, inductive
Ohmic switching current
typ. 4 A AC/DC per channel
Inductive switching current
typ. 2 A AC/DC per channel
Minimum permitted load
typ. 0.1 mA at 0.1 V
DC
(at 120 operations / min)
Electrical isolation
500 V (K-bus / field voltage)
K-Bus current consumption
Typ. 120 mA
Bit width in process image
4 outputs
Switching cycles mech. (min.)
2 x 10
7
(at 18 x 10
3
switching cycles per hour)
Switching cycles electr. (min.)
1 x 10
5
(3 A at 30 V
DC
and ohmic load)
Configuration
No address or configuration settings
Contact resistance (max.)
typ. 100 mΩ
Insulation
resistance (min.)
typ. 1000 MΩ at 500 V
DC
Pluggable wiring
for all KSxxxx terminals
Weight
approx. 70 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm support rail according to EN 60715
Permissible ambient temperature range
during operation
0 °C ... +55 °C
Permissible ambient temperature range
during storage
-25 °C ... +85 °C
Relative humidity
95% no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Approvals/markings
CE, UKCA, EAC