Mounting and wiring
KL17xx/KS17xx
20
Version: 4.1.0
Fig. 10: Power contact on left side
NOTE
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230 V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10 mm from the group of terminals.
WARNING
Risk of electric shock!
The PE power contact must not be used for other potentials!
Содержание KL17 Series
Страница 1: ...Documentation EN KL17xx KS17xx Digital input terminals 2021 08 04 Version 4 1 0...
Страница 2: ......
Страница 4: ...Table of contents KL17xx KS17xx 4 Version 4 1 0...
Страница 33: ......