Product overview
KL17xx/KS17xx
15
Version: 4.1.0
2.3.1
Technical data
Technical data
KL1722, KS1722
Connection technology
2 wire
Number of counters
2
Nominal voltage
120/230 V
AC
Signal voltage ‘0’
0 V … 40 V
Signal voltage ‘1’
79 V … 260 V
Input filter
typ. 10 ms
Input current
> 3 mA, typ. 6 mA
Current consumption from K-bus typ. 3 mA
Switching times
10 ms
Electrical isolation
500 V (K-bus / field voltage), 3750 V
AC
, 1 min.
Bit width in process image
2 input bits
Configuration
no address or configuration settings required
Special features
resistive/capacitive input behavior
Weight
app. 60 g
Permissible ambient temperature
during operation
0°C ... +55°C
Permissible ambient temperature
during storage
-25°C ... +85°C
Permissible relative humidity
95 %, no condensation
Vibration / shock resistance
according to EN 60068-2-6 / EN 60068-2-27, refer also to
Installation instructions for enhanced mechanical load capacity [
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Pluggable wiring
for all KSxxxx terminals
Approvals/markings
CE, UKCA, cULus, EAC, GL, ATEX
Ex marking
Standard
Marking
ATEX
II 3 G Ex nA IIC T4 Gc
Содержание KL17 Series
Страница 1: ...Documentation EN KL17xx KS17xx Digital input terminals 2021 08 04 Version 4 1 0...
Страница 2: ......
Страница 4: ...Table of contents KL17xx KS17xx 4 Version 4 1 0...
Страница 33: ......