Mounting and wiring
KL1xxx
40
Version: 1.0.0
3.4
ATEX - Special conditions (standard temperature
range)
WARNING
Observe the special conditions for the intended use of Beckhoff fieldbus components with
standard temperature range in potentially explosive areas (directive 2014/34/EU)!
• The certified components are to be installed in a suitable housing that guarantees a protection class of at
least IP54 in accordance with EN 60079-15! The environmental conditions during use are thereby to be
taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in points of cables, lines or
pipes, or higher than 80°C at the wire branching points, then cables must be selected whose tempera-
ture data correspond to the actual measured temperature values!
• Observe the permissible ambient temperature range of 0 to 55°C for the use of Beckhoff fieldbus compo-
nents standard temperature range in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being exceeded by more than
40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus Terminal system if the supply
voltage has been switched off or if a non-explosive atmosphere is ensured!
• The connections of the certified components may only be connected or disconnected if the supply volt-
age has been switched off or if a non-explosive atmosphere is ensured!
• The fuses of the KL92xx/EL92xx power feed terminals may only be exchanged if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has been switched off or if
a non-explosive atmosphere is ensured!
Standards
The fundamental health and safety requirements are fulfilled by compliance with the following standards:
• EN 60079-0:2012+A11:2013
• EN 60079-15:2010
Marking
The Beckhoff fieldbus components with standard temperature range certified according to the ATEX directive
for potentially explosive areas bear one of the following markings:
II 3G KEMA 10ATEX0075 X Ex nA IIC T4 Gc Ta: 0 … +55°C
or
II 3G KEMA 10ATEX0075 X Ex nC IIC T4 Gc Ta: 0 … +55°C
Содержание KL1 Series
Страница 1: ...Documentation KL1xxx Digital input terminals 24 V DC 1 0 0 2020 05 08 Version Date...
Страница 2: ......
Страница 9: ...Product overview KL1xxx 9 Version 1 0 0 2 2 KL1002 KL1012 Introduction Fig 1 KL1002 Fig 2 KL1012...
Страница 13: ...Product overview KL1xxx 13 Version 1 0 0 2 3 KL1104 KL1114 Introduction Fig 5 KL1104 Fig 6 KL1114...
Страница 16: ...Product overview KL1xxx 16 Version 1 0 0 2 4 KL1402 KL1412 Introduction Fig 8 KL1402 Fig 9 KL1412...
Страница 19: ...Product overview KL1xxx 19 Version 1 0 0 2 5 KL1404 KL1414 KL1434 Introduction Fig 11 KL1404 Fig 12 KL1414...
Страница 25: ...Product overview KL1xxx 25 Version 1 0 0 Fig 18 KL1488 Fig 19 KL1498...
Страница 29: ...Product overview KL1xxx 29 Version 1 0 0 2 7 KL1862 KL1862 0010 KL1872 Introduction Fig 22 KL1862 Fig 23 KL1872...