Parameterization and commissioning
EL6752
46
Version: 2.1
Baud rate
The baud rate is set here.
Cycle time
Displays the cycle time of the corresponding highest priority task. The display is updated when the mapping
is generated. The network variables are updated with the cycle of this task.
Watchdog time
Time until the watchdog is triggered
Search...
Searches for all available EL6752-0010 channels, from which the required channel can be selected. In the
case of an FC5102 both channels A and B appear. These behave in logical terms like two FC5101 cards.
Firmware
Displays the current EL6752-0010 firmware version.
Firmware Update...
Updates the EL6752-0010 firmware. Attention: The TwinCAT System must be stopped for this function.
“ADS” tab
Fig. 39: “ADS” tab
The EL6752-0010 is an ADS device with its own net ID, which can be changed here. All ADS services
(diagnostics, acyclic communication) associated with the EL6752-0010 device must address the card via this
NetID. Additional ADS Net IDs can be entered for addressing subordinate ADS devices (e.g. an additional
fieldbus card in the same PC) via the card.
"(Online) DPRAM" tab
Read access to the DPRAM of the card is provided for diagnostic purposes.
Box EL6752-0010 slave
A box "EL6752-0010 (DeviceNet slave)" is created automatically. Further parameters have to be set: