Commissioning and configuration
EP9300-0022
42
Version: 2.3
Fig. 24: Inserting a "generic channel" (in the case of IO-Link devices from other manufacturers)
IO-Link devices from Beckhoff are automatically added with the required parameters. For devices from other
manufacturers please use a generic channel and select the process data size.
Configuration of the IO-Link device
The minimum settings required for operating an IO-Link device are:
IO-Link version: Generally 1.1; enter 11
Frame capability: Generally 1
Min. cycle time: Generally 2.3 ms, i.e. 23
Process data in / Out length: Variable (number in bits), for a size of 2 bytes input enter 16 for "Process data
in length".
Master control: set to IO-Link
All other settings are optional.