Operation
EL6900
55
Version: 2.2.0
Index
Name
Meaning
Flags
Default
FA00:0 Diag
The following sub-indices contain detailed diagnostic
information.
RO
FA00:03 Temperature
error
0005
hex
Maximum temperature exceeded
RO
0000
hex
0006
hex
Temperature fell below minimum
0007
hex
Temperature difference between the measuring
points exceeded
Supply error 0101
hex
max. supply voltage µC1 exceeded
0102
hex
max. supply voltage µC2 exceeded
0103
hex
voltage fell below min. supply voltage µC1
0104
hex
voltage fell below min. supply voltage µC2
Note
Differing diagnostic messages possible
Due to the variable order or execution of the test series, diagnostic messages differing from
those given in the table above are possible.
Index F100
hex
: Device Status
This CoE object is also mapped to the EL6900 process image under DEVICE Inputs.
Index
Name
Meaning
Data type
Flags
F100:01 Safety
Project State
State of the Safety Logic Project
BIT3
RO
0
OFFLINE
Safety Project not loaded
1
RUN
Safety Project is executed, EtherCAT is in SAFEOP
or OP state
2
STOP
Safety Project is loaded, but is stopped, due to a
logged in user
3
START
Safety Project is loaded, EtherCAT is in INIT or
PREOP state
4
RESTORE
When RESTORE Mode is configured: Project CRC is
read from the FSoE Slaves
7
FAULT
The EL6900 has switched off due to a severe fault. A
safety project can not be loaded or started.
F100:08 Login Active A user is logged in to the EL6900
BOOLEAN RO
F100:09 Input Size
Mismatch
The length of the input data does not match the input data
length calculated from the safety Logic
BOOLEAN RO
F100:0A Output Size
Mismatch
The length of the output data does not match the output data
length calculated from the safety Logic
BOOLEAN RO
F100:0F TxPDO
State
This bit is set, when the Safety Project State is unequal to
RUN
BOOLEAN RO
F100:10 TxPDO
Toggle
This bit is toggled each time the EtherCAT input data is
updated for the first time after it has been read by the
EtherCAT master.
BOOLEAN RO
Содержание EL6900
Страница 1: ...Operating Instructions for EL6900 TwinSAFE Logic Terminal 2 2 0 2017 05 10 Version Date...
Страница 2: ......
Страница 34: ...Operation EL6900 34 Version 2 2 0 Fig 18 Creating a TwinSAFE group...
Страница 37: ...Operation EL6900 37 Version 2 2 0 Fig 22 Appended Emergency Stop block...
Страница 59: ...Appendix EL6900 59 Version 2 2 0 5 2 Certificates...
Страница 60: ...Appendix EL6900 60 Version 2 2 0...