Parameterization and commissioning
EL6731
50
Version: 2.8
PKW Read
ADS-Read parameters
Meaning
Net-ID
Net-ID of the master (see the device's
Port
station address of the slave
IndexGroup
Bit 0-11: parameter number (PNU)
Bit 12-25: 0
Bit 26: 1 = Sub-index in octet 3 (standard), 0 = sub-index in octet 4
(Simodrive 611U)
Bit 27: 1 = ARRAY codes are not supported by PROFIDRIVE slave
Bit 28-31: axis number (for single axis modules always 1)
IndexOffset
Sub-index (for ARRAY access)
Length
Parameter length: 2 or 4
Data
In response: Parameter value
PKW Write
ADS-Write parameters
Meaning
Net-ID
Net-ID of the master (see the device's
Port
station address of the slave
IndexGroup
Bit 0-11: parameter number (PNU)
Bit 12-25: 0
Bit 26: 1 = Sub-index in octet 3 (standard), 0 = sub-index in octet 4
(Simodrive 611U)
Bit 27: 1 = ARRAY codes are not supported by PROFIDRIVE slave
Bit 28-31: axis number (for single axis modules always 1)
IndexOffset
Sub-index (for ARRAY access)
Length
Parameter length: 2 or 4
Data
In request: Parameter value
PKW ReadNoOfArrayElements
ADS-Read parameters
Meaning
Net-ID
Net-ID of the master (see the device's
Port
station address of the slave
IndexGroup
Bit 0-11: parameter number (PNU)
Bit 12-15: 0
Bit 16: 1
Bit 17-25: 0
Bit 26: 1 = Sub-index in octet 3 (standard), 0 = sub-index in octet 4
(Simodrive 611U)
Bit 27: 1 = ARRAY codes are not supported by PROFIDRIVE slave
Bit 28-31: axis number (for single axis modules always 1)
IndexOffset
0
Length
Parameter length: 1
Data
In response: Number of the parameter 's array elements