Product overview
EL6731
15
Version: 2.8
2.2
Technical data
Technical data
EL6731-0000
EL6731-0010
Bus system
PROFIBUS DP (standard),
PROFIBUS DP-V1 (Cl. 1+2: acyclic services, alarms),
PROFIBUS DP-V2, PROFIBUS MC (equidistance)
Version
Master
Slave
Number of fieldbus channels
1
Data transfer rate
9.6 kbaud to 12 Mbaud
Bus interface
1 x D-Sub socket, 9-pin, galvanically isolated
Bus nodes
maximum 125 slaves with up to 244 bytes input, output,
parameter, configuration or diagnostic data per slave
Cycle time
Differing DP cycle times per slave are possible using the CDL
concept
Process image
Sum max.: 1.4 kbyte input and 1.4 kbyte output data
Diagnostics
Status LEDs
Power supply
via the E-bus
Current consumption via E-bus
typ. 350 mA
Electrical isolation
500 V (E-bus/Profibus)
Configuration
with TwinCAT System Manager
Weight
approx. 70 g
Permissible ambient temperature range
during operation
-25 °C ... +60 °C (extended Temperature range) (for
EL6731-0010 from Hardware 17)
Permissible ambient temperature range
during storage
-40 °C ... +85 °C
Permissible relative humidity
95 %, no condensation
Dimensions (W x H x D)
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE