Commissioning
EL3182
101
Version: 1.2
Vendor calibration, index 0x80n0:0B
The vendor calibration is enabled via index 0x80n0:0B. Parameterization takes place via the indices
• 0x80nF:01 Vendor calibration: Offset
• 0x80nF:02 Vendor calibration: Gain
User calibration, index 0x80n0:0A
The user calibration is enabled via index 0x80n0:0A. Parameterization takes place via the indices
• 0x80n0:17 User calibration: Offset
• 0x80n0:18 User calibration: Gain
User scaling, index 0x80n0:01
The user scaling is enabled via index 0x80n0:01. Parameterization takes place via the indices
• 0x80n0:11 User scaling: Offset
• 0x80n0:12 User scaling: Gain
Producer Codeword
Beckhoff reserves the right to implement the basic calibration of the terminals. The Producer code-
word is therefore at present reserved.
5.4.2
Parameterization
An EL31xx is parameterized via 2 dialog boxes/tabs in the TwinCAT System Manager, the Process Data tab
(A) for the communication-specific settings and the CoE directory (B) for the settings in the slave.
Fig. 104: EL31xx parameterization
• Changes to the process data-specific settings are generally only effective after a restart of the
EtherCAT master:
Restart TwinCAT in RUN or CONFIG mode; RELOAD in CONFIG mode