Operation
EL2911
40
Version: 1.0.0
Index
Name
Default value/
unit
Description
8010:01
ModuloDiagTestPulse
0x00 / integer
Modulo value for the frequency of
generating a test pulse.
0 -> every time
1 -> every 2nd time
...
8010:02
MultiplierDiagTestPulse
0x01 / integer
Length of the test pulse in multiples of
400 µs
8010:04
Diag TestPulse active
TRUE / Boolean Activation of test pulses for the
corresponding input module
8011:01
Channel1.InputFilterTime
0x0014 / 0.1 ms Input filter of the safe input. Following this
time the internal input signal changes to
the applied signal state.
Internal test pulses can have a length of
up to 2 ms and cannot can be switched
off.
8011:02
Channel1.DiagTestPulseFilterTime 0x0002 / 0.1 ms Input filter for the test pulse signal
8011:04
Channel2.InputFilterTime
0x0014 / 0.1 ms Input filter of the safe input. Following this
time the internal input signal changes to
the applied signal state.
Internal test pulses can have a length of
up to 2 ms and cannot can be switched
off.
8011:05
Channel2.DiagTestPulseFilterTime 0x0002 / 0.1 ms Input filter for the test pulse signal
8011:07
Channel3.InputFilterTime
0x0014 / 0.1 ms Input filter of the safe input. Following this
time the internal input signal changes to
the applied signal state.
Internal test pulses can have a length of
up to 2 ms and cannot can be switched
off.
8011:08
Channel3.DiagTestPulseFilterTime 0x0002 / 0.1 ms Input filter for the test pulse signal
8011:0A
Channel4.InputFilterTime
0x0014 / 0.1 ms Input filter of the safe input. Following this
time the internal input signal changes to
the applied signal state.
Internal test pulses can have a length of
up to 2 ms and cannot can be switched
off.
8011:0B
Channel4.DiagTestPulseFilterTime 0x0002 / 0.1 ms Input filter for the test pulse signal